A 100 km transmission line is designed for a nominal voltage of 132 kV and consists of one conductor per phase. The line reactance is 0.726 Ω/km. The static transmission capacity of the line, in Megawatts, would be
132
240
416
720
240
B is correct because the calculated static transmission capacity of the transmission line is 240 MW.
Nominal voltage V = 132 kV, Transmission line length L = 100 km, Reactance per unit length x = 0.726 Ω/km.
Pmax=XV2
Calculate total reactance
The total reactance of the line is the product of the length and reactance per km. X=100 km×0.726 Ω/km=72.6 Ω.
X=100×0.726=72.6 Ω
Apply static power capacity formula
The static transmission capacity (theoretical power limit) assumes a power angle of δ=90°, given by P=XV2.
P=72.6(132×103)2
Perform calculation
Calculate the value in Watts and convert to Megawatts (MW) by dividing by 106.
P=72.617424×106≈240×106 W=240 MW
B is correct because the calculated static transmission capacity of the transmission line is 240 MW.
This formula P=XV2 is the fundamental limit for steady-state stability in power systems, often taught alongside the Swing Equation in stability analysis.