Join 60,000+ competitive exam aspirants
A power system is subjected to a fault which makes the zero sequence component of current equal to zero. The nature of fault is
Double line to ground fault
Double line fault
Line to ground fault
Three-phase to ground fault
Double line fault
In a power system, the zero-sequence component of current (I0тАЛ) exists only when there is a path for the current to flow into the ground. A double-line fault (line-to-line fault without ground) does not involve the ground, hence the zero-sequence current is zero.
In a power system, the zero-sequence component of current (I0тАЛ) exists only when there is a path for the current to flow into the ground. A double-line fault (line-to-line fault without ground) does not involve the ground, hence the zero-sequence current is zero.
I0тАЛ=31тАЛ(IaтАЛ+IbтАЛ+IcтАЛ) тАФ Definition of zero-sequence current component
IaтАЛ+IbтАЛ+IcтАЛ=0 тАФ Kirchhoff's Current Law for non-grounded faults
In symmetrical component analysis, the zero-sequence current is defined as I0тАЛ=31тАЛ(IaтАЛ+IbтАЛ+IcтАЛ). In a balanced system or a line-to-line fault where no current path to the neutral/ground exists, the sum of phase currents is zero, leading to I0тАЛ=0. For faults involving the ground (L-G, LL-G, LLL-G), at least one path to ground exists, causing a non-zero I0тАЛ.
Zero-sequence current is an indicator of the presence of a ground return path.
Double line (LL) faults are balanced in terms of ground involvement (none).
Positive and negative sequence networks are connected in parallel for an LL fault.
Zero sequence network is open-circuited for faults without ground connection.
Simplifies analysis of unsymmetrical faults using sequence networks.
Helps in relay coordination by identifying fault types.
Does not provide information about the exact location of the fault.
Assumes linear system behavior which may not hold during heavy saturation.
Protective relay setting calculation.
Power system stability analysis.
Fault current level determination.
| Feature | L-G or LL-G Fault | Double Line (LL) Fault |
|---|---|---|
Zero Sequence Current (I0тАЛ) | Non-Zero | Zero |
The zero-sequence network is essentially the path for current flowing through the neutral and ground.
Option C (Line to ground fault) involves a ground return path, so I0тАЛюАа=0.
Option D (Three-phase fault) is a balanced fault where I0тАЛ=0, but it is not an unsymmetrical fault.
B is correct тАФ In a double line fault, there is no path to the ground, resulting in the sum of phase currents being zero and thus the zero-sequence current component is zero.
Always remember: If the fault does not involve the earth (ground), the sum of the phase currents IaтАЛ+IbтАЛ+IcтАЛ is always zero, rendering the zero-sequence component I0тАЛ zero.