A single-phase transmission line of impedance j 0.8 Ω supplies a resistive load of 500 A at 300 V. The sending-end power factor is
Unity
0.8 lagging
0.8 leading
0.6 lagging
0.6 lagging
D is correct because the sending-end voltage VS leads the reference current by 53.13°, resulting in a power factor of cos(53.13°)=0.6 lagging.
Load voltage VL = 300 V, Load current I = 500 A (resistive), Line impedance Zline = j 0.8 Ω
Vs=VL+I⋅Zline,cosϕs=VsIsPs
Calculate the Voltage Drop
Since the load is resistive, the current I is in phase with the load voltage VL. Let VL=300∠0° V and I=500∠0° A. The voltage drop across the impedance is ΔV=I⋅Zline=500⋅(j0.8)=j400 V.
ΔV=j400 V
Calculate the Sending-end Voltage
The sending-end voltage VS is the phasor sum of load voltage and voltage drop: VS=VL+ΔV=300+j400.
VS=300+j400=500∠53.13° V
Determine the Power Factor
The sending-end power factor angle is the angle of VS because the current I is at 0°. Thus, the power factor is cos(53.13°). Since VS leads I, the current lags the sending-end voltage.
cos(53.13°)=0.6 (lagging)
D is correct because the sending-end voltage VS leads the reference current by 53.13°, resulting in a power factor of cos(53.13°)=0.6 lagging.
In transmission line analysis, the sending-end power factor is always evaluated relative to the sending-end voltage VS. If VS=VR+IZ, the phase angle difference represents the lagging/leading nature.