Join 60,000+ competitive exam aspirants
A synchronous machine has higher capacity for
Leading power factor
Lagging power factor
Power factor of the load
None of above
Leading power factor
A synchronous machine, specifically a synchronous condenser, has a higher capacity for leading power factor operation because over-excitation allows the machine to supply reactive power (Q>0) to the grid. In this state, the machine acts like a capacitor, improving the overall system power factor by compensating for inductive loads.
A synchronous machine, specifically a synchronous condenser, has a higher capacity for leading power factor operation because over-excitation allows the machine to supply reactive power (Q>0) to the grid. In this state, the machine acts like a capacitor, improving the overall system power factor by compensating for inductive loads.
Q=XsтАЛVтАЛ(EbтАЛcos╬┤тИТV) тАФ Reactive power equation of a synchronous machine
EbтАЛ>VтЯ╣Leading┬аPower┬аFactor тАФ Condition for over-excitation
When a synchronous motor is over-excited, its induced back EMF (EbтАЛ) exceeds the terminal voltage (V). This causes the machine to draw a leading current from the supply. By adjusting the field excitation, the synchronous condenser can provide variable reactive power support, effectively acting as a static synchronous compensator to stabilize system voltage.
Over-excitation (EbтАЛ>V) results in leading power factor.
Under-excitation (EbтАЛ<V) results in lagging power factor.
Synchronous machines are frequently used as condensers for power factor correction.
Leading power factor operation is beneficial for voltage regulation in long transmission lines.
Provides smooth and adjustable reactive power support.
Improves system voltage stability and power factor.
Can be used for dynamic compensation.
Requires complex control circuitry for excitation.
Has higher maintenance requirements compared to static capacitors.
Higher initial cost.
Power system voltage regulation
Reactive power compensation in industrial grids
Maintaining stable bus voltages in transmission networks
The capacity to operate at a leading power factor is physically limited by the field winding thermal rating.
Option B (Lagging) occurs during under-excitation, where the machine consumes reactive power like an inductor.
A is correct тАФ A synchronous machine exhibits a higher capacity for leading power factor operation when over-excited, allowing it to supply reactive power to the system.
Always remember: Over-excited Synchronous Motor = Capacitor (Leading); Under-excited Synchronous Motor = Inductor (Lagging).