A system is said to be effectively grounded if its
Neutral is grounded directly
Ratio of X1тАЛX0тАЛтАЛ>3.0
Ratio of X1тАЛR0тАЛтАЛ>2.0
Ratio of X1тАЛX0тАЛтАЛ<3.0
Ratio of X1тАЛX0тАЛтАЛ<3.0
A power system is considered effectively grounded (or solidly grounded) if the ratio of the zero-sequence reactance (X0тАЛ) to the positive-sequence reactance (X1тАЛ) is less than 3.0. Additionally, the ratio of the zero-sequence resistance (R0тАЛ) to the positive-sequence reactance (X1тАЛ) must be less than 1.0.
A power system is considered effectively grounded (or solidly grounded) if the ratio of the zero-sequence reactance (X0тАЛ) to the positive-sequence reactance (X1тАЛ) is less than 3.0. Additionally, the ratio of the zero-sequence resistance (R0тАЛ) to the positive-sequence reactance (X1тАЛ) must be less than 1.0.
X1тАЛX0тАЛтАЛ<3.0 тАФ Reactance ratio requirement
X1тАЛR0тАЛтАЛ<1.0 тАФ Resistance ratio requirement
Effective grounding is designed to limit the overvoltage on the unfaulted phases during a single line-to-ground fault. By maintaining a low X0тАЛ/X1тАЛ ratio, the neutral point of the system remains close to the ground potential, which significantly reduces the displacement of the neutral and protects the insulation levels of the equipment.
Effective grounding minimizes Transient Recovery Voltage (TRV).
It allows the use of graded insulation for transformers.
It restricts the rise in voltage of sound phases to approximately 80% of line-to-line voltage during a ground fault.
Reduced insulation costs for equipment.
Easier detection of ground faults via relaying.
Significant reduction in transient overvoltages.
Higher fault current magnitudes require circuit breakers with higher ratings.
Increased risk of inductive interference with communication circuits.
Extra High Voltage (EHV) transmission systems.
Systems where standard insulation levels are to be kept economical.
Option B (Ratio > 3.0) represents an ungrounded or Petersen coil grounded system condition.
Standard industrial practice defines effective grounding to ensure protection coordination simplicity.
D is correct тАФ The condition for effective grounding is that the ratio of zero-sequence reactance to positive-sequence reactance must be less than 3.0, ensuring controlled phase-to-ground voltages.
Always remember that X0тАЛ is highly dependent on the grounding method, whereas X1тАЛ and X2тАЛ are inherent to the machine/line geometry and remain relatively constant.