An alternator is supplying a load of 300 kW at a power factor of 0.6 lagging. If the power factor is raised to 0.9 lagging, how much more kW can alternator supply ?
200 kW
450 kW
90 kW
150 kW
150 kW
An alternator is rated by its apparent power (kVA), which remains constant regardless of the power factor. When the power factor is improved from 0.6 to 0.9, the reactive power component decreases, allowing a greater portion of the kVA capacity to be utilized as active power (kW).
An alternator is rated by its apparent power (kVA), which remains constant regardless of the power factor. When the power factor is improved from 0.6 to 0.9, the reactive power component decreases, allowing a greater portion of the kVA capacity to be utilized as active power (kW).
S=cos╬жPтАЛ тАФ Apparent power relationship
╬ФP=S(cos╬ж2тАЛтИТcos╬ж1тАЛ) тАФ Additional power capacity formula
The apparent power S of an alternator is defined as S=cos╬жPтАЛ. Since S is constant, P1тАЛ=SтЛЕcos╬ж1тАЛ and P2тАЛ=SтЛЕcos╬ж2тАЛ. By maintaining the same total kVA loading, the improvement in power factor increases the real power output limit.
Alternators are designed based on kVA ratings due to current limitations in windings.
Higher power factor means less reactive current flows for the same real power output.
Improving power factor reduces transmission line losses and increases effective load capacity.
Increased effective load capacity of existing machinery
Improved voltage regulation of the alternator
Requires installation of capacitor banks or synchronous condensers
Potential risk of over-correction leading to leading power factor issues
Industrial power plant capacity optimization
Distribution system efficiency enhancement
The initial kVA is 300/0.6=500 kVA.
The new power at 0.9 pf is 500├Ч0.9=450 kW.
The additional power is 450тИТ300=150 kW.
Option B (450 kW) is the total power capacity, not the 'more' power supplied.
D is correct тАФ The alternator can supply an additional 150 kW because the total kVA capacity is fixed at 500 kVA.
Always verify if the question asks for total capacity or additional capacity to avoid common pitfalls like selecting 450 kW instead of 150 kW.