Join 60,000+ competitive exam aspirants
Bundled conductors in EHV transmission system provide
Reduced capacitance
Increased capacitance
Increased inductance
Increased voltage gradient
Increased capacitance
Bundled conductors are used in EHV transmission lines to reduce the corona effect and radio interference. By replacing a single conductor with a bundle of two or more conductors per phase, the Geometric Mean Radius (GMR) of the conductor arrangement is increased, which effectively increases the line capacitance.
Bundled conductors are used in EHV transmission lines to reduce the corona effect and radio interference. By replacing a single conductor with a bundle of two or more conductors per phase, the Geometric Mean Radius (GMR) of the conductor arrangement is increased, which effectively increases the line capacitance.
C=ln(D/GMReqтАЛ)2╧А╧╡0тАЛтАЛ тАФ Capacitance of a transmission line
GMReqтАЛ=nnтЛЕrтЛЕdnтИТ1тАЛ тАФ Equivalent GMR for n sub-conductors of radius r and bundle spacing d
In a bundle arrangement, the effective radius (ReqтАЛ) of the conductor is larger than that of a single solid conductor. The capacitance of a transmission line is inversely proportional to the natural logarithm of the ratio of the distance between conductors to the effective radius of the conductor. As the effective radius increases, the capacitance per unit length increases, while the inductance decreases.
Bundling increases the Geometric Mean Radius (GMR) of the phase.
Higher capacitance facilitates reactive power compensation requirements.
Bundling reduces the surface voltage gradient, thereby mitigating corona loss.
Inductance is reduced due to the increase in GMR.
Reduction in corona loss and radio interference
Increase in surge impedance loading (SIL) capacity
Reduction in line inductance
Increased power transfer capability
Higher wind loading on towers
Increased cost due to more conductor material and spacers
More complex structural design for towers
Extra High Voltage (EHV) transmission lines (>220kV)
Ultra High Voltage (UHV) transmission lines
Option A is incorrect because bundling increases, not decreases, capacitance.
Option C is incorrect because bundling decreases the equivalent inductance of the line.
Option D is incorrect because bundling reduces the voltage gradient by increasing the effective surface area.
B is correct тАФ Bundled conductors increase the effective radius (GMR) of the phase, which leads to an increase in the shunt capacitance of the transmission line.
Always remember that GMR is inversely proportional to Inductance and directly related to the effective surface area, which inversely affects Voltage Gradient and directly affects Capacitance.