By increasing the transmission voltage to double of its original value the same power can be dispatched keeping the line loss
Equal to original value
Half the original value
Double the original value
One fourth of original value
One fourth of original value
When the transmission voltage is doubled while maintaining the same power transfer, the load current is halved. Since power loss (line loss) in a conductor is proportional to the square of the current (I2R), halving the current results in the power loss decreasing to one-fourth of its original value.
When the transmission voltage is doubled while maintaining the same power transfer, the load current is halved. Since power loss (line loss) in a conductor is proportional to the square of the current (I2R), halving the current results in the power loss decreasing to one-fourth of its original value.
P=VIcos╧Х тАФ Relation between Power, Voltage, and Current
PlossтАЛ=I2R тАФ Calculation of copper/line loss
PlossтА▓тАЛ=(2IтАЛ)2R=41тАЛI2R тАФ Derivation for double voltage
In an electrical power transmission system, power delivered is given by P=VIcos╧Х. To keep P constant while doubling V, the current I must become IтА▓=I/2. The transmission line power loss is defined as PlossтАЛ=I2R. Substituting the new current IтА▓=I/2, the new loss becomes PlossтА▓тАЛ=(I/2)2R=41тАЛI2R=41тАЛPlossтАЛ.
High voltage transmission is preferred to reduce line losses and improve efficiency.
Reducing current allows for smaller conductor cross-section (saving material costs).
Line loss is directly proportional to the square of the current.
Voltage levels are stepped up using transformers at the generating station.
Lower I┬▓с┤┐ losses
Reduced conductor material cost
Improved voltage regulation
Enhanced transmission efficiency
Higher insulation costs
Increased tower height requirements
Corona discharge risk at extremely high voltages
Long-distance power transmission (HVAC/HVDC)
Grid interconnectors
Substation design
The inverse square relationship holds provided the power factor and the power delivered remain constant.
Option A is incorrect as doubling voltage reduces, not maintains, the loss.
Option B and C imply a linear relationship which is incorrect for I2R losses.
D is correct тАФ Since power loss is proportional to the square of the current (I2R), doubling the voltage reduces the current by half, which results in a reduction of the line loss to one-fourth of its initial value.
Always remember that transmission losses are dominated by the square of the current (I2R); focusing on current reduction is the primary goal of high-voltage transmission engineering.