Join 60,000+ competitive exam aspirants
Capacitance grading of cable implies
Use of dielectrics of different permeabilities
Grading according to the capacitance of cables per km length
Cables using single dielectric in different concentrations
Capacitance required to be introduced at different lengths to counter the effect of inductance
Use of dielectrics of different permeabilities
Capacitance grading in high-voltage cables is a technique used to achieve a uniform electrostatic stress distribution across the insulation. This is accomplished by using layers of dielectric materials with different permittivities (╧╡)such that the potential gradient is constant throughout the insulation thickness.
Capacitance grading in high-voltage cables is a technique used to achieve a uniform electrostatic stress distribution across the insulation. This is accomplished by using layers of dielectric materials with different permittivities (╧╡)such that the potential gradient is constant throughout the insulation thickness.
g=xln(R/r)VтАЛ тАФ Electric stress at distance x from the center of the conductor.
╧╡1тАЛr1тАЛ=╧╡2тАЛr2тАЛ=╧╡3тАЛr3тАЛ тАФ Condition for uniform stress distribution in graded insulation layers.
In a single-dielectric cable, the electrostatic stress (electric field intensity) is maximum at the conductor surface and minimum at the sheath. By using dielectrics with decreasing permittivity (higher near the conductor, lower near the sheath), we ensure the product of permittivity and electric field intensity (╧╡E) remains constant, which results in a more uniform stress distribution and reduces the insulation volume required for a given voltage rating.
Uniform stress allows for a more compact cable design.
Grading minimizes the possibility of dielectric breakdown.
Permittivity must decrease as the distance from the conductor increases.
Commonly achieved by using impregnated paper with varying compositions.
Improved dielectric strength utilization.
Reduction in overall cable diameter for a specific voltage.
Increased manufacturing complexity and cost.
Difficulty in maintaining precise permittivity layers over long cable runs.
High-voltage underground transmission cables.
Specialized HVDC power cabling.
Option B refers to length-based capacitance, which relates to transmission line parameters rather than insulation grading.
Capacitance grading is fundamentally different from sheath grading (inter-sheath grading), though both aim to equalize stress.
A is correct тАФ Capacitance grading involves utilizing multiple dielectric materials with varying permittivities to achieve a uniform electrostatic stress gradient.
Remember that in HV cables, the highest electrical stress is always at the conductor surface; grading aims to shift this stress toward the outer layers to prevent premature puncture.