Join 60,000+ competitive exam aspirants
Considering two parallel short transmission lines of impedance ZA and ZB respectively.┬аCurrent IA and IB are both lagging and sending end voltage is VтВЫ. If the reactance to resistance ratio of both the impedance ZA and ZB are equal then total current I will be
Lagging by both IAтАЛ and IBтАЛ
Leading by both IAтАЛ and IBтАЛ
In phase with both IAтАЛ and IBтАЛ
None of above
In phase with both IAтАЛ and IBтАЛ
When two parallel lines have identical X/R ratios, their impedance angle ╬╕=tanтИТ1(X/R) is identical. Consequently, both branch currents IAтАЛ and IBтАЛ have the same phase angle relative to the sending end voltage VsтАЛ, causing them to be in phase with each other.
When two parallel lines have identical X/R ratios, their impedance angle ╬╕=tanтИТ1(X/R) is identical. Consequently, both branch currents IAтАЛ and IBтАЛ have the same phase angle relative to the sending end voltage VsтАЛ, causing them to be in phase with each other.
╬╕AтАЛ=╬╕BтАЛ=tanтИТ1(RAтАЛXAтАЛтАЛ)=tanтИТ1(RBтАЛXBтАЛтАЛ) тАФ Equality of impedance angles
I=IAтАЛтАЛ+IBтАЛтАЛ=VsтАЛтАЛ(ZAтАЛ1тАЛ+ZBтАЛ1тАЛ) тАФ Total current calculation
The current in a line is given by I=ZVsтАЛтАЛтАЛ. Since ZAтАЛтАЛ=тИгZAтАЛтИгтИа╬╕ and ZBтАЛтАЛ=тИгZBтАЛтИгтИа╬╕, both currents lag the voltage VsтАЛ by the same angle ╬╕. If two vectors lag a reference vector by the same angle, the angle between the two vectors themselves is zero, meaning they are in phase.
Parallel branches with identical impedance angles force branch currents to have identical power factors.
The total current I is simply the vector sum of IAтАЛ and IBтАЛ, which are collinear.
This condition simplifies load sharing calculations in power system analysis.
Uniform power factor distribution.
Simplifies parallel line balancing calculations.
Requires impedance matching of lines.
Not always physically achievable in existing networks.
Parallel transmission line modeling.
Load flow studies in power grids.
The condition RAтАЛXAтАЛтАЛ=RBтАЛXBтАЛтАЛ ensures that the reactive power to active power ratio is identical for both branches.
Option A and B are incorrect because the phase shift relative to VsтАЛ is fixed for both lines due to the matching impedance angles.
C is correct тАФ Since both lines have equal X/R ratios, their impedance phase angles are identical, resulting in IAтАЛ and IBтАЛ having the same phase angle, making them in phase with each other.
Always check the X/R ratio when dealing with parallel branches; if they are equal, the currents will always be in phase with each other regardless of the magnitude of the individual impedances.