Constant voltage transmission line has the drawback of
Increase of short circuit current of the system
Lower reserve of line in case of line trouble
Increased risk of interruption of supply due to falling of synchronous motors out of synchronism
All of above
All of above
A constant voltage transmission system maintains a fixed voltage at the receiving end regardless of load variations by using synchronous condensers or static VAR compensators. While this stabilizes voltage, it introduces significant technical drawbacks including increased short-circuit current duty, higher capital cost, and reduced stability margins during system disturbances.
A constant voltage transmission system maintains a fixed voltage at the receiving end regardless of load variations by using synchronous condensers or static VAR compensators. While this stabilizes voltage, it introduces significant technical drawbacks including increased short-circuit current duty, higher capital cost, and reduced stability margins during system disturbances.
VRтАЛ=VSтАЛтИТI(R+jX) тАФ Basic transmission voltage drop relation
IscтАЛ=ZeqтАЛVтАЛ тАФ Short circuit current magnitude definition
The system utilizes shunt compensation (usually over-excited synchronous motors or SVCs) to supply the reactive power required by the load. By injecting reactive power locally, the voltage drop I(Rcos╧Х+Xsin╧Х) is negated. However, keeping the voltage fixed during a fault leads to higher fault currents due to the low impedance presented by the compensators, and synchronous machines connected to the bus become more prone to instability because the system lacks the natural 'stiffness' associated with larger impedance-driven voltage drops.
Constant voltage transmission relies on local reactive power injection.
Higher fault current ratings are required for switchgear due to the lower effective impedance.
Synchronous motors are sensitive to supply voltage stability and may pull out of synchronism if the voltage fluctuates during a fault.
System complexity increases due to the need for continuous control equipment.
Superior voltage regulation at the receiving end
Increased transmission capacity for long lines
Improved power factor at the load end
Higher short-circuit current
Increased risk of loss of synchronism
Higher maintenance and capital cost
Requirement for synchronous condensers or SVCs
Long-distance EHV transmission lines
Industrial grids with high reactive power loads
Synchronous condensers are often used in these systems to provide dynamic reactive power support.
The 'reserve of line' refers to the stability margin; in a constant voltage system, the system operates closer to its theoretical limit, leaving less room for handling faults or load swings (transient stability).
D is correct тАФ All listed factors are recognized technical disadvantages resulting from the implementation of a constant voltage transmission control scheme.
Always remember that in power systems, there is a trade-off between voltage regulation and short-circuit capacity; improving the former almost always increases the latter.