Diversity factor in a power system is
Always less than one
Normally less than one
Always more than one
Normally more than one
Always more than one
The diversity factor is defined as the ratio of the sum of individual maximum demands of various consumers to the simultaneous maximum demand of the entire group. Since the maximum demands of individual consumers do not occur at the same time, the sum of individual maximum demands is always greater than the system's actual maximum demand.
The diversity factor is defined as the ratio of the sum of individual maximum demands of various consumers to the simultaneous maximum demand of the entire group. Since the maximum demands of individual consumers do not occur at the same time, the sum of individual maximum demands is always greater than the system's actual maximum demand.
DF=Pmax,groupтАЛтИСi=1nтАЛPmax,iтАЛтАЛ тАФ Diversity Factor calculation where Pmax,iтАЛ is the individual max demand.
In a power system, consumers have different load profiles due to varying usage patterns and habits. Because peak demands of individual loads are staggered throughout the day, the aggregate peak demand on the supply station is less than the sum of individual peak demands. This statistical non-coincidence ensures the denominator of the diversity factor formula is always smaller than the numerator, resulting in a value greater than unity.
It is a measure of the diversity of load patterns among consumers.
A higher diversity factor indicates better utilization of the distribution system capacity.
It is always greater than 1 because of the non-simultaneous nature of peak loads.
Economic benefit: A higher diversity factor reduces the required rating of generation and distribution equipment.
Enables reduction in total installed capacity requirements.
Improves the capital efficiency of power network infrastructure.
Increases complexity in planning and forecasting.
System stability might be challenged if load patterns shift simultaneously (e.g., mass EV charging).
Power system planning and distribution design.
Tariff determination and load scheduling.
A value of 1 would imply that all consumers reach their peak demand at the exact same instant, which is practically impossible in a large-scale system.
Option A and B are incorrect because they describe factors like Load Factor or Utilization Factor which are typically тЙд1.
C is correct тАФ The diversity factor is always greater than one because the sum of individual maximum demands exceeds the simultaneous maximum demand of the entire group.
Do not confuse Diversity Factor (always > 1) with Load Factor (ratio of average load to peak load, always < 1). Remember: Diversity = Diversity (Group vs Individual), Load = Utilization (Average vs Peak).