For a 2-wire ac single phase distribution system operating at โ30โ MW and โ315โ kV, operating at the power factor of 0.8 having 15ฮฉ of resistance of each wire, then the copper loss at the substation in kW is
105.33
108.27
210.67
240.87
210.67
Practice and solve "For a 2-wire ac single phase distribution system operating at โ30โ MW and โ315โ kV, operating at the..." for Electrical - Power System. The correct answer is Option C: 210.67. Detailed step-by-step solution, conceptual clarity, and formulas on Examoogle.