For fully transposed transmission line
Equal positive and negative sequence impedance
Zero sequence impedance much larger than positive sequence impedance
Both (a) and (b)
None of the above
Both (a) and (b)
A fully transposed transmission line ensures symmetry across its length by rotating conductor positions. This symmetry leads to equal positive and negative sequence impedances (Z1тАЛ=Z2тАЛ) and results in a zero sequence impedance (Z0тАЛ) that is significantly higher than the positive/negative sequence impedances due to the higher ground return path resistance and self/mutual inductance.
A fully transposed transmission line ensures symmetry across its length by rotating conductor positions. This symmetry leads to equal positive and negative sequence impedances (Z1тАЛ=Z2тАЛ) and results in a zero sequence impedance (Z0тАЛ) that is significantly higher than the positive/negative sequence impedances due to the higher ground return path resistance and self/mutual inductance.
Z1тАЛ=Z2тАЛ
Z0тАЛтЙИ2.5┬аto┬а3.5├ЧZ1тАЛ
Transposition equalizes the mutual inductance and shunt capacitance between phases over the length of the line. Because the system becomes balanced, the negative sequence network is identical to the positive sequence network. However, the zero sequence current flows through the ground/earth, making Z0тАЛ dependent on the grounding path, which is much higher than the phase-conductor-based positive/negative sequence paths.
Transposition prevents unbalanced voltage drops.
Positive sequence impedance depends on conductor geometry and GMD.
Zero sequence impedance depends on earth resistivity and the physical tower structure.
In a perfectly transposed line, the off-diagonal elements of the sequence impedance matrix become zero.
Reduces interference with communication lines.
Equalizes phase voltage drops.
Simplifies power system stability calculations.
Increases structural complexity and cost of transmission towers.
Requires additional hardware at transposition points.
Long distance high voltage transmission lines.
Systems sensitive to inductive interference.
The zero sequence impedance Z0тАЛ is significantly larger because it includes the impedance of the ground return path, which is not present in positive or negative sequence networks.
If a line is not transposed, the sequence networks become coupled, which complicates fault analysis.
C is correct тАФ For a fully transposed transmission line, the symmetry makes positive and negative sequence impedances equal, while the path of zero sequence current through the ground makes its impedance significantly higher.
Always remember that Z1тАЛ and Z2тАЛ are identical for all static equipment (like transmission lines and transformers) because they do not depend on the direction of phase rotation.