For high voltage, ac circuit breakers, the rated short circuit current is passed for
10 seconds
1 sec
3 seconds
0.01 sec
1 sec
The rated short-time withstand current for high voltage AC circuit breakers is passed for a standard duration of 1 second (sec) or 3 seconds depending on system rating. In standard switchgear testing and objective exam conventions, when unspecified, the short-circuit current duration is conventionally rated for 1┬аsec (or up to 3┬аsec per IEC/IS standards).
IS/IEC 62271-100 Cl. 5.101, IEEE C37.04
The rated short-time withstand current for high voltage AC circuit breakers is passed for a standard duration of 1 second (sec) or 3 seconds depending on system rating. In standard switchgear testing and objective exam conventions, when unspecified, the short-circuit current duration is conventionally rated for 1┬аsec (or up to 3┬аsec per IEC/IS standards).
H=I2тЛЕRтЛЕt тАФ Thermal energy dissipated during fault (Joule heating)
ImakingтАЛ=2.55├ЧIbreakingтАЛ тАФ Peak short-circuit making current rating
During a symmetrical short-circuit fault, high thermal stresses occur due to I2t heating and high mechanical stresses occur due to electrodynamic forces proportional to I2. Circuit breakers must withstand these thermal and mechanical stresses without damage or excessive temperature rise until protective relays operate and isolate the fault.
Rated short-time withstand current is the RMS value of short-circuit current that a breaker can carry in closed position for a specified duration.
Standard rated short-circuit duration specified by IS/IEC standards is 1┬аsec or 3┬аsec.
Prevents thermal damage to breaker contacts and busbars during temporary fault conditions.
Ensures proper coordination with upstream and downstream protective relays.
Carrying high short-circuit currents for longer durations requires heavier conductor cross-sections and stronger mechanical support structures.
High Voltage Substation Switchgear Protection
Generating Station Main Circuit Breakers
Option A (10┬аsec) is too long and causes extreme thermal damage to contacts.
Option B (1┬аsec) represents the standard short-time withstand current rating duration.
Option D (0.01┬аsec) corresponds to half a cycle at 50┬аHz, which is much shorter than standard short-time withstand ratings.
B is correct тАФ The rated short-circuit current for high voltage circuit breakers is specified to be carried for a short-time withstand duration of 1 second (or 3 seconds according to standard specifications).
Remember that Making Current =2.55├ЧBreaking┬аCurrent (peak) and Short-Time Current is specified for 1┬аsec or 3┬аsec (RMS).