Join 60,000+ competitive exam aspirants
For single frequency transients, ratio of peak restriking voltage to time between voltage zero and peak voltage is called
Restriking voltage
Recovery voltage
Rate of rising restriking voltage
Active recovery voltage
Rate of rising restriking voltage
The Rate of Rise of Restriking Voltage (RRRV) is defined as the ratio of the peak restriking voltage to the time taken to reach that peak voltage during single-frequency transient conditions. It measures how rapidly the transient voltage across the breaker contacts rises immediately following current zero interruption. A higher RRRV increases the likelihood of re-ignition across the circuit breaker contacts.
IEC 62271-100 / IS 13118:1991
The Rate of Rise of Restriking Voltage (RRRV) is defined as the ratio of the peak restriking voltage to the time taken to reach that peak voltage during single-frequency transient conditions. It measures how rapidly the transient voltage across the breaker contacts rises immediately following current zero interruption. A higher RRRV increases the likelihood of re-ignition across the circuit breaker contacts.
v(t)=VmтАЛ(1тИТcos╧ЙnтАЛt) тАФ Restriking voltage transient waveform
Vm,peakтАЛ=2VmтАЛ=2VpeakтАЛ тАФ Peak value of restriking voltage
tnтАЛ=╧ЙnтАЛ╧АтАЛ=╧АLCтАЛ тАФ Time to reach peak restriking voltage
RRRVavgтАЛ=tnтАЛVm,peakтАЛтАЛ=╧АLCтАЛ2VmтАЛтАЛ тАФ Average rate of rise of restriking voltage
RRRVmaxтАЛ=(dtdvтАЛ)maxтАЛ=╧ЙnтАЛVmтАЛ=LCтАЛVmтАЛтАЛ тАФ Maximum rate of rise of restriking voltage
When a circuit breaker opens to interrupt a fault current, the arc is extinguished at a current zero. The system voltage attempts to establish itself across the opening contacts, generating a high-frequency transient called the restriking voltage. The speed at which this voltage rises is governed by the system inductance (L) and capacitance (C). If the rate of dielectric strength recovery between the contacts is slower than the RRRV, the arc re-ignites.
RRRV depends directly on the natural frequency of oscillation ╧ЙnтАЛ=LCтАЛ1тАЛ of the circuit.
Higher natural frequency results in higher RRRV, making arc extinction more difficult.
Resistance switching (connecting a resistor RтЙд21тАЛCLтАЛтАЛ across circuit breaker contacts) is used to damp restriking voltage transients and limit RRRV.
Sizing and selecting circuit breakers based on short-circuit transient duties.
Designing resistance switching schemes for circuit breakers to reduce transient overvoltages.
Active recovery voltage is the instantaneous power-frequency voltage existing across the circuit breaker contacts at the instant of arc extinction (VactiveтАЛ=K1тАЛK2тАЛK3тАЛVmтАЛsin╧Х).
Option A (Restriking voltage) refers to the entire transient voltage that appears across circuit breaker contacts at or near current zero.
Option B (Recovery voltage) is the power-frequency RMS voltage that appears across circuit breaker contacts after final arc extinction.
C is correct тАФ By definition, the ratio of peak restriking voltage to the time taken to reach peak voltage is the Average Rate of Rise of Restriking Voltage (RRRV).
In competitive exams like GATE and ESE, remember that RRRVmaxтАЛ=╧ЙnтАЛVmтАЛ occurs at ╧ЙnтАЛt=2╧АтАЛ, whereas RRRVavgтАЛ=╧АLCтАЛ2VmтАЛтАЛ occurs over time tnтАЛ=╧АLCтАЛ.