Which of the following is not a type test of CB?
Dielectric test
electrical endurance test
verification of overload performance
DC resistance mesurement
DC resistance mesurement
DC resistance measurement is a routine or maintenance test for checking contact resistance and winding resistance, but it is not classified as a type test of a circuit breaker. Type tests are performed on a prototype breaker to verify its basic design characteristics and ratings as per standard specifications like IEC 62271-100 or IS 13118.
IEC 62271-100 Cl. 6 / IS 13118
DC resistance measurement is a routine or maintenance test for checking contact resistance and winding resistance, but it is not classified as a type test of a circuit breaker. Type tests are performed on a prototype breaker to verify its basic design characteristics and ratings as per standard specifications like IEC 62271-100 or IS 13118.
Vdrop=Idc×Rcontact — Contact resistance measurement using micro-ohmmeter
Irated≤Imaking/2.55 — Relationship between peak making current and RMS short-circuit current
Type tests are intended to prove the rated capability, insulation level, and mechanical/electrical integrity of a newly designed circuit breaker under extreme specified conditions. Routine tests, such as DC resistance measurement of the main circuit, are conducted on every individual breaker manufactured to ensure quality control and proper assembly before commissioning.
Type tests are performed once on a prototype unit to validate the fundamental design against standard rating requirements.
Routine tests are conducted on every manufactured unit before dispatch to verify proper assembly and operation.
Dielectric tests, short-circuit breaking tests, temperature rise tests, and mechanical endurance tests are all standard type tests per IEC 62271-100.
| Feature | Type Test | Routine Test |
|---|---|---|
Purpose | To prove design parameters and capability | To check quality and defect-free manufacturing |
Frequency | Performed once on a prototype unit | Performed on every manufactured breaker unit |
Example Tests | Dielectric, short-circuit, electrical endurance | DC resistance, power-frequency withstand, visual inspection |
Option A (Dielectric test): Evaluates the impulse and power frequency insulation withstand capabilities (Type Test).
Option B (Electrical endurance test): Verifies the ability of the circuit breaker contacts to handle rated operations without excessive erosion (Type Test).
Option C (Verification of overload performance): Tests thermal performance under continuous/overload currents (Type Test).
Option D (DC resistance measurement): Used routinely to measure main contact resistance (typically in micro-ohms) to ensure proper joint tightness.
D is correct — DC resistance measurement is a routine test conducted on every breaker to measure contact resistance, whereas options A, B, and C are standardized type tests.
Always remember: Type tests validate Design, Routine tests validate Delivery/Manufacturing, and Commissioning tests validate Site Installation.