Examoogle
ExamsTest SeriesRank CheckPrevious Year PapersPassBook StoreMy BooksAI Tutor
🛒0
अA
Examoogle

India's most trusted platform for competitive exam PDF books. Expert-authored, watermark-protected, instant access.

Exams & Practice
All Exams & SyllabusMock Test SeriesPrevious Year PapersPractice Questions (MCQs)Recruitment Notifications
Quick Links
Examoogle AI TutorExam NewsBook StoreMy BooksLogin / Sign Up
Support
About UsRefund PolicyPrivacy PolicyTerms of UseContact Us
© 2026 Examoogle. India's #1 competitive exam AI tutor.
🔒 SSL Secured📱 UPI Accepted🧾 GST Invoice
Examoogle

Join 60,000+ competitive exam aspirants

or with email
By continuing, you agree to ourTerms of Service&Privacy Policy
Your Cart
Subtotal₹0
Total₹0
Examoogle • User • info@examoogle.com • EE-2024-8821
Chapter 1 of 12 • Page 1 of 248🔒 Protected PDF • Watermarked
Back to Practice Questions
ElectricalPower System
PrevNext

How many terminals are there in Earth Loop Tester?

A

3

B

2

C

1

D

5

Correct Answer

Concept & PrincipleElectricalPower System
Option C

1

Quick Summary: An earth loop tester is an electrical test instrument designed to measure the impedance of the earth fault loop path. It utilizes three terminals—typically designated as Line (L), Neutral (N), and Earth (E)—to simulate a fault condition and measure the resistance/impedance of the path back to the supply source transformer.

💡 Explanation

An earth loop tester is an electrical test instrument designed to measure the impedance of the earth fault loop path. It utilizes three terminals—typically designated as Line (L), Neutral (N), and Earth (E)—to simulate a fault condition and measure the resistance/impedance of the path back to the supply source transformer.

🔢 Key Formulas

Zs=Ze+R1+R2Z_s = Z_e + R_1 + R_2Zs​=Ze​+R1​+R2​ — where ZsZ_sZs​ is the total loop impedance, ZeZ_eZe​ is external impedance, and R1,R2R_1, R_2R1​,R2​ are cable resistances

If=U0ZsI_f = \frac{U_0}{Z_s}If​=Zs​U0​​ — where IfI_fIf​ is the prospective fault current and U0U_0U0​ is the nominal voltage to earth

⚙️ Working Principle

When connected, the tester injects a momentary current between the Line and the Protective Earth (PE) conductor. By measuring the voltage drop and the current injected (I=VZI = \frac{V}{Z}I=ZV​), the instrument calculates the loop impedance (ZsZ_sZs​) using Ohm's Law. This ensures that in the event of an insulation failure, the fault current is high enough to trip the protective circuit breaker or fuse within the required time.

📌 Key Points
  • ▸

    The 3-terminal configuration ensures accurate measurement of the path loop impedance.

  • ▸

    Correct testing is mandatory for the operation of RCDs (Residual Current Devices) and MCBs (Miniature Circuit Breakers).

  • ▸

    Measurement includes the transformer winding resistance and the supply cable impedance.

✅ Advantages
  • ▸

    Ensures safety by verifying disconnection times.

  • ▸

    Detects high resistance joints in the earth continuity conductor.

❌ Disadvantages / Limitations
  • ▸

    Can cause RCDs to trip during measurement if not configured correctly.

  • ▸

    Requires isolation or special 'no-trip' technology.

🛠️ Applications / Uses
  • ▸

    Electrical installation testing for residential buildings.

  • ▸

    Industrial earthing system compliance checks.

📄 Additional Information
  • ▸

    Standard loop impedance values are governed by the IET Wiring Regulations (BS 7671 or equivalent local standards).

  • ▸

    Option B (2 terminals) is common for continuity testers but insufficient for full loop impedance measurement.

📊 Diagram / Illustration
Earth Loop Tester TerminalsLine (L)Neutral (N)Earth (E)3-Terminal Interface
✅

A is correct — Earth Loop Testers typically utilize three terminals (Line, Neutral, and Earth) to measure the total impedance of the earth fault loop path.

Core Concepts Used
Click any tag to open in AI Tutor
Earth Fault Loop Impedance Protective Earth Electrical Safety Testing
💡 EXAM TIP

Remember that loop impedance must be low enough to allow sufficient fault current to flow, ensuring the protective device disconnects supply within specified time limits (e.g., 0.4s or 5s).

Related Questions

ElectricalPower System
The specified quantities of Generation bus is
ElectricalPower System
When an alternator connected to the bus-bar is shut down the bus-bar voltage will
ElectricalPower System
The current drawn by the line due to corona losses is _______
ElectricalPower System
The specified quantities of load bus are
ElectricalPower System
The advantages of high transmission voltage are ______

Discussion (0)

Loading discussion...
PrevNext