Join 60,000+ competitive exam aspirants
HV transmission line uses
Pin type insulator
Suspension type insulator
Both (a) and (b)
None of above
Both (a) and (b)
High voltage (HV) transmission lines utilize various types of insulators to provide electrical isolation and mechanical support between the conductors and the transmission towers. While pin type insulators are typically limited to lower voltages (up to 33 kV) due to size and flashover constraints, suspension type insulators are modular and are extensively used for HV and EHV lines to manage higher voltage levels effectively.
High voltage (HV) transmission lines utilize various types of insulators to provide electrical isolation and mechanical support between the conductors and the transmission towers. While pin type insulators are typically limited to lower voltages (up to 33 kV) due to size and flashover constraints, suspension type insulators are modular and are extensively used for HV and EHV lines to manage higher voltage levels effectively.
VstringтАЛ=V1тАЛ+V2тАЛ+...+VnтАЛ тАФ Total voltage withstand of a string of n insulators
String┬аEfficiency=n├ЧVoltageacrossunitnearesttoconductorTotalVoltageтАЛ├Ч100
The suspension insulator consists of several porcelain or toughened glass discs connected in a series string. As voltage levels increase, the number of units in the string is increased proportionally to maintain the desired dielectric strength and creepage distance. This modular design allows for flexibility, mechanical strength, and ease of replacement in HV systems.
Pin insulators are rigid and generally restricted to lower distribution voltages.
Suspension insulators are used for voltages above 33 kV.
String efficiency decreases as the number of discs in a suspension string increases.
The potential distribution across a suspension string is non-uniform due to shunt capacitance.
Suspension type offers higher mechanical strength for long spans.
Easy to replace individual faulty discs in a suspension string.
Better flexibility for changing voltage levels by adding/removing discs.
Pin insulators become bulky and uneconomical at higher voltages.
Suspension insulators require greater tower height to maintain ground clearance.
Complex voltage distribution necessitates grading rings in EHV lines.
Distribution lines (Pin type)
Transmission lines 66kV to 765kV (Suspension type)
| Feature | Pin Type | Suspension Type |
|---|---|---|
Voltage Level | Up to 33 kV | 33 kV to 765 kV+ |
Construction | Rigid | Flexible/Modular |
The question implies that both types are relevant to the broad category of overhead lines, though specifically, suspension insulators are the primary choice for HV.
Pin insulators are rarely used beyond 33 kV because the size of the porcelain shed becomes too large to be manufactured safely.
C is correct тАФ HV transmission lines typically employ suspension insulators due to their modularity and ability to withstand high voltage levels effectively.
Always remember that for transmission voltage V>33┬аkV, suspension insulators are mandatory because the electrical stress at the conductor pin of a rigid insulator becomes unmanageable.