If 132 kV line passes over a residential building, the minimum vertical clearance from the roof of the building should be
57 m
5 m
6 m
3 m
57 m
According to the Indian Electricity Rules, 1956 (now superseded by CEA Measures relating to Safety and Electric Supply Regulations, 2010), the minimum vertical clearance for a 132 kV line from the top of a building is 4.57 meters (commonly rounded to 4.6 meters). The provided option '57 m' in the question is a typographical error representing '4.57 m'.
According to the Indian Electricity Rules, 1956 (now superseded by CEA Measures relating to Safety and Electric Supply Regulations, 2010), the minimum vertical clearance for a 132 kV line from the top of a building is 4.57 meters (commonly rounded to 4.6 meters). The provided option '57 m' in the question is a typographical error representing '4.57 m'.
VclтАЛтЙе4.57┬аm тАФ Minimum vertical clearance requirement for 132 kV lines over buildings
Vertical clearance is mandated to prevent accidental contact with energized conductors and to mitigate the effects of the electric field on the building structure and occupants. These regulations account for the maximum sag under extreme ambient temperatures and wind conditions, ensuring that even at the lowest point of the span, the dielectric strength of the air gap remains sufficient to prevent flashover.
Safety standards are governed by the CEA (Central Electricity Authority) Measures relating to Safety and Electric Supply Regulations.
Clearance is measured from the lowest sag point of the conductor to the highest accessible part of the building (e.g., roof, parapet).
Voltage levels directly influence the air gap required to maintain insulation integrity under varying atmospheric conditions.
The value 4.57 meters is standard for voltage ranges between 33 kV and 132 kV.
Prevents accidental electrical shocks for residents.
Reduces the risk of arcing or flashover due to induction or proximity.
Limits urban vertical construction planning near transmission corridors.
Requires significant land usage or easement rights.
Transmission line routing and planning.
Urban civil engineering and building safety certification.
The option '57 m' provided in the question is a truncated version of the correct value '4.57 m'.
For voltages above 132 kV, additional clearances are required based on a calculation of 0.3 meters per every additional 33 kV beyond the base voltage level.
A is correct тАФ The minimum vertical clearance required by Indian regulations for a 132 kV line over a building is 4.57 meters.
Always remember that for 132 kV, the vertical clearance is 4.57 m, and for any higher voltage, you add 0.3 m for every 33 kV increment.