If three transformers in a ∆ − ∆ are delivering their rated load and one transformer is removed, then overload on each of the remaining transformers is ......... percent.
57.7
66.66
73.2
86.66
73.2
When a single transformer is removed from a ∆−∆ transformer system, the load on each remaining transformer increases due to the redistribution of the total load among fewer units. This causes each of the two remaining transformers to be overloaded by approximately 73.2 percent.
When a single transformer is removed from a ∆−∆ transformer system, the load on each remaining transformer increases due to the redistribution of the total load among fewer units. This causes each of the two remaining transformers to be overloaded by approximately 73.2 percent.
Overload=Original LoadNew Load−Original Load×100 — indicates the percentage overload
New Load=23L — load on each transformer after one is removed
In a balanced three-transformer system, each transformer shares one-third of the total load. If one transformer is taken out of service, the entire load is divided equally between the two remaining transformers, resulting in each taking on 150% of the original 100% load, leading to a 73.2% overload (25% increase on the original load).
Each transformer initially shares an equal load in a ∆−∆ configuration.
Removing one transformer results in an increased load on the remaining transformers.
Redundancy in design
Load balancing under optimal conditions
Increased risk of overheating
Possible damage during overload condition
Industrial power distribution
Electrical substations
Standard overload conditions lead to thermal and mechanical stress.
Option A is incorrect as it underestimates the overload percentage.
C is correct — Each remaining transformer in the system is subjected to a 73.2% overload after one transformer is removed.
Understanding load management can also help in topics related to circuit design and power systems.