In a substation, current transformers are used to
Measuring purpose
Protection purpose
Both Measuring and Protection purpose
None of these
Both Measuring and Protection purpose
Current Transformers (CTs) serve a dual role in power systems: they step down high primary currents to safe, standardized values (typically 1A or 5A) for sensitive monitoring equipment and provide isolated signals for protective relays. They are classified based on their core characteristics, such as accuracy class for measurement and saturation characteristics for protection.
Current Transformers (CTs) serve a dual role in power systems: they step down high primary currents to safe, standardized values (typically 1A or 5A) for sensitive monitoring equipment and provide isolated signals for protective relays. They are classified based on their core characteristics, such as accuracy class for measurement and saturation characteristics for protection.
IsтАЛ=IpтАЛ├ЧNsтАЛNpтАЛтАЛ тАФ Transformation ratio relationship
K=NpтАЛNsтАЛтАЛ тАФ Turns ratio
The CT operates on the principle of electromagnetic induction where the primary winding carries the load current. The secondary winding, having a large number of turns, produces a proportional secondary current IsтАЛ=IpтАЛ├ЧNsтАЛNpтАЛтАЛ. For protection, the CT must maintain linearity under high fault conditions, whereas for measurement, it requires high accuracy during normal operating conditions.
CTs isolate measurement devices from high voltage primary circuits.
Measuring CTs are designed to saturate at low current levels to prevent damage during faults.
Protection CTs are designed not to saturate until high fault currents occur, ensuring relay reliability.
The secondary of a CT must never be kept open-circuited while the primary is energized.
Galvanic isolation between high voltage and low voltage circuits.
Safety for personnel and equipment by using low-current standardized secondary values.
Open secondary causes high flux in the core leading to high voltage buildup and insulation failure.
Phase shift error and ratio error in non-ideal CTs.
Energy billing meters and ammeters.
Overcurrent and differential protection relays.
Measuring CTs are defined by high accuracy near rated current.
Protection CTs are defined by Accuracy Limit Factor (ALF) to handle fault current.
C is correct тАФ Current transformers are designed to feed both measuring instruments (for monitoring) and protective relays (for system isolation during faults).
Remember that CT secondary terminals should always be shorted when not connected to a load to prevent fatal high-voltage buildup due to core saturation.