In a three unit insulator string, voltage across the lowest unit is 17.5 kV and string efficiency is 84.28%. The total voltage across the string will be equal to
8.825 kV
44.25 kV
88.25 kV
442.5 kV
44.25 kV
B is correct because the calculated total voltage across the three-unit string is approximately 44.25 kV.
Number of insulator units n = 3, Voltage across lowest unit Vn = 17.5 kV, String efficiency η = 84.28% = 0.8428
η=n×VnVtotal
Define string efficiency formula
String efficiency is defined as the ratio of the total voltage across the string to the product of the number of units and the voltage across the lowest unit.
η=n×VnVtotal
Rearrange formula for total voltage
To find the total voltage Vtotal, rearrange the efficiency formula: Vtotal=η×n×Vn.
Vtotal=η×n×Vn
Substitute given values and calculate
Substitute n=3, η=0.8428, and Vn=17.5 kV into the equation.
Vtotal=0.8428×3×17.5=44.247
B is correct because the calculated total voltage across the three-unit string is approximately 44.25 kV.
In power systems, string efficiency is always less than 100% due to the shunt capacitance of the insulator units; adding grading rings or using insulators with different capacitances can improve this efficiency.