__________ is the terms expressed the highest number of short-circuit current that the breakers are capable of breaking under specified conditions of transient recovery voltage and power frequency voltage.
Rated current
Short Circuit Current
Breaking Capacity
Making Capacity
Breaking Capacity
Breaking capacity of a circuit breaker is defined as the highest value of short-circuit current that the breaker is capable of breaking safely under specified conditions of transient recovery voltage (TRV) and power frequency voltage. It is expressed in kA (RMS value) or MVA.
IS/IEC 60947-2, IEC 62271-100
Breaking capacity of a circuit breaker is defined as the highest value of short-circuit current that the breaker is capable of breaking safely under specified conditions of transient recovery voltage (TRV) and power frequency voltage. It is expressed in kA (RMS value) or MVA.
SbтАЛ=3тАЛ├ЧV├ЧIbтАЛ тАФ Symmetrical Breaking Capacity in MVA
ImakeтАЛ=2.55├ЧIbтАЛ тАФ Relation between Making Capacity (peak) and Breaking Capacity (symmetrical RMS)
When a fault occurs, the contacts of the circuit breaker separate, initiating an arc between them. The breaker must extinguish this arc against the rising transient recovery voltage (TRV) that appears across the contacts. The maximum current it can successfully interrupt without thermal or dielectric re-ignition defines its breaking capacity.
Breaking capacity is always expressed as an RMS value of current in kA.
Making capacity accounts for the maximum instantaneous peak current during the first major loop, which includes DC asymmetry.
The multiplication factor 2.55 comes from 2тАЛ├Ч1.8 (where 1.8 accounts for the DC offset factor in power systems).
Ensures circuit breaker selection handles peak short-circuit levels safely.
Prevents catastrophic failure due to explosive arc restrikes during fault opening.
Higher breaking capacity requires larger arc chutes and costlier interruption media (SF6/Vacuum).
Selection and sizing of circuit breakers in sub-stations and power transmission networks.
Short-circuit coordination studies.
| Feature | Breaking Capacity | Making Capacity |
|---|---|---|
Definition | Max short-circuit current the breaker can safely open/interrupt. | Max short-circuit current the breaker can safely close onto. |
Value Type | RMS value (kA) | Peak value (kA) |
Relative Magnitude | Lower (IbтАЛ) | Higher (2.55├ЧIbтАЛ) |
Option A (Rated Current) refers to the continuous normal operating current without exceeding temperature limits.
Option B (Short Circuit Current) is a general term for fault current flowing in the circuit.
Option D (Making Capacity) is the peak current the breaker can close against during a fault.
C is correct тАФ Breaking Capacity represents the highest RMS short-circuit current that a breaker can interrupt under specified transient recovery and power frequency voltage conditions.
Remember that Making Capacity is a PEAK value (2.55├ЧIbтАЛ), while Breaking Capacity is an RMS value тАФ a frequent numerical distinction in GATE and ESE exams!