Lightening arrester should be located
Near the circuit breaker
Away from the circuit breaker
Near the transformer
Away from the transformer
Near the transformer
A lightning arrester is placed as close to the transformer as possible to minimize the length of the conductor between them. This placement ensures that surge voltages resulting from traveling waves are clamped before reaching the transformer's sensitive insulation.
A lightning arrester is placed as close to the transformer as possible to minimize the length of the conductor between them. This placement ensures that surge voltages resulting from traveling waves are clamped before reaching the transformer's sensitive insulation.
VtotalтАЛ=VdischargeтАЛ+LdtdiтАЛ тАФ Voltage experienced by the transformer
BIL>VarresterтАЛ тАФ Safety condition for transformer insulation
When a surge wave travels along a transmission line, it experiences reflection and refraction at impedance discontinuities, such as at a transformer terminal. If the arrester is far from the transformer, the inductive voltage drop v=LdtdiтАЛ across the lead wire increases the effective discharge voltage at the transformer, potentially exceeding its Basic Insulation Level (BIL). By minimizing the lead length, we reduce the additive voltage drop and ensure the transformer is protected by the arrester's protective characteristics.
The lightning arrester must be located as close to the equipment being protected as physically possible.
The lead wire length is critical; excessive length causes high inductive voltage drop during rapid surge currents.
The purpose is to shunt the surge current to the ground before it stresses the transformer windings.
Prevents transformer winding insulation failure
Limits transient overvoltages effectively
Provides a low impedance path for lightning surges
Increased system complexity near the transformer
Requires regular maintenance and inspection
Adds capacitive load if not properly designed
Power transformers in substations
Distribution transformer protection
High-voltage transmission line termination
Option A is incorrect because the arrester's primary purpose is to protect specific equipment like the transformer, not just the circuit breaker.
Option B and D are incorrect as increasing the distance allows reflected waves to increase the stress beyond the arrester's protection level.
C is correct тАФ The lightning arrester is placed near the transformer to minimize the inductive voltage drop across the connecting leads and ensure the surge voltage remains below the transformer's insulation withstand level.
Always remember that lead inductance L acts as a low-pass filter for high-frequency transients; minimize lead length to keep the protection voltage V low.