Over excited synchronous phase modifier
Draws a lagging current
Draws a leading current
Supplies a leading current
Supplies a lagging current
Draws a leading current
An over-excited synchronous motor, when running at no-load, acts as a synchronous phase modifier (or synchronous condenser). In this state, it draws a leading current from the supply to provide reactive power, which improves the power factor of the system.
An over-excited synchronous motor, when running at no-load, acts as a synchronous phase modifier (or synchronous condenser). In this state, it draws a leading current from the supply to provide reactive power, which improves the power factor of the system.
EbтАЛ>V тАФ Condition for over-excitation
Q=VIaтАЛsin╧Х тАФ Reactive power supplied by the phase modifier
When a synchronous motor is over-excited, its induced back EMF (EbтАЛ) becomes greater than the supply voltage (V). This causes the machine to supply reactive volt-amperes to the source, essentially acting like a capacitor. In this condition, the armature current leads the supply voltage, allowing it to compensate for lagging loads in a power system.
Synchronous phase modifiers are used for power factor correction in large transmission systems.
The excitation current (IfтАЛ) is kept higher than the normal value to achieve the over-excited state.
It does not perform any mechanical work and runs at no-load.
Stepless control of power factor
Voltage regulation improvement
Can be used in conjunction with capacitors
Higher maintenance compared to static capacitors
Introduces rotational losses
Higher initial cost
Power transmission substations
Large industrial plants to improve power factor
Voltage stability enhancement
Under-excited synchronous motors draw lagging current (behave like inductors).
Normal excited synchronous motors operate at unity power factor.
B is correct тАФ An over-excited synchronous motor behaves as a capacitive load, drawing leading current from the power supply.
Always remember: Over-excited machines are capacitive (leading), while under-excited machines are inductive (lagging). This rule applies to both synchronous motors and synchronous generators (in terms of reactive power exchange).