Per unit impedance of a circuit element is 0.3. if the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be
0.3
0.6
0.003
0.006
0.6
Given: Initial per unit impedance (Z_pu_old) = 0.3, Base kV is halved (kVnewтАЛ = 0.5 * kVoldтАЛ), Base MVA is halved (MVAnewтАЛ = 0.5 * MVAoldтАЛ).
Initial per unit impedance (Z_pu_old) = 0.3, Base kV is halved (kVnewтАЛ = 0.5 * kVoldтАЛ), Base MVA is halved (MVAnewтАЛ = 0.5 * MVAoldтАЛ).
Zpu,newтАЛ=Zpu,oldтАЛ├Ч(MVAoldтАЛMVAnewтАЛтАЛ)├Ч(kVnewтАЛkVoldтАЛтАЛ)2
Identify the per unit impedance formula
The per unit impedance ZpuтАЛ is given by the formula ZpuтАЛ=(kVbaseтАЛ)2ZactualтАЛ├ЧMVAbaseтАЛтАЛ.
ZpuтАЛ=(kVbaseтАЛ)2ZactualтАЛ├ЧMVAbaseтАЛтАЛ
Relate old and new values
Given MVAnewтАЛ=0.5├ЧMVAoldтАЛ and kVnewтАЛ=0.5├ЧkVoldтАЛ. The actual impedance ZactualтАЛ of the element remains constant.
ZactualтАЛ=Zpu,oldтАЛ├ЧMVAoldтАЛ(kVoldтАЛ)2тАЛ=Zpu,newтАЛ├ЧMVAnewтАЛ(kVnewтАЛ)2тАЛ
Calculate the new per unit impedance
Substituting the new base values into the equality: Zpu,newтАЛ=Zpu,oldтАЛ├ЧMVAoldтАЛMVAnewтАЛтАЛ├Ч(kVnewтАЛkVoldтАЛтАЛ)2. Plugging in the ratios: Zpu,newтАЛ=0.3├Ч(0.5)├Ч(1/0.5)2.
Zpu,newтАЛ=0.3├Ч0.5├Ч4=0.6
B is correct because the new per unit impedance is calculated to be 0.6 when the MVA base is halved and the kV base is squared in the denominator.
This concept is vital in power system analysis, particularly for fault studies and load flow calculations where multiple voltage levels exist in a single system.