Ratio of puncture┬а voltage to the flash over voltage of a line insulator is
Equal to 1
Less than 1
Greater than 1
None of above
Greater than 1
The ratio of puncture voltage to flashover voltage is known as the safety factor of the insulator. It is always designed to be greater than 1 so that the insulator flashes over externally through the air rather than puncturing internally through the porcelain material.
The ratio of puncture voltage to flashover voltage is known as the safety factor of the insulator. It is always designed to be greater than 1 so that the insulator flashes over externally through the air rather than puncturing internally through the porcelain material.
Safety┬аFactor=FlashoverVoltagePunctureVoltageтАЛ тАФ defines the ratio for insulator protection
Insulators are designed to be stronger internally (dielectric strength) than externally (air path). If the puncture voltage were less than or equal to the flashover voltage, a voltage surge would lead to the permanent breakdown of the dielectric material, which is irreversible and catastrophic. A higher puncture strength ensures that any abnormal overvoltage results in an external arc, which can be cleared once the fault is removed without damaging the insulator itself.
Puncture refers to the disruptive discharge through the solid body of the insulator.
Flashover refers to the disruptive discharge through the surrounding air medium.
Permanent damage occurs during puncture, whereas flashover is generally non-destructive.
The typical value for pin-type insulators is approximately 10.
Protects the insulator from permanent dielectric breakdown.
Ensures system reliability under voltage surges.
Higher safety factors require larger insulator dimensions, increasing weight and cost.
Overhead transmission line strings.
Distribution line pin insulators.
If the ratio were equal to 1, both phenomena would be equally likely, leading to a high risk of permanent insulator failure.
If the ratio were less than 1, the insulator would fail by puncture long before an external arc could form, destroying the equipment.
C is correct тАФ The ratio is kept greater than 1 to ensure that the insulator undergoes an external flashover rather than an internal puncture during overvoltage conditions.
Always remember that in power systems, we design components such that the weakest point is one that can recover naturally, like air gaps, rather than solid materials that suffer permanent damage.