Screened type cables, over belted cables has advantage of
Reduced possibility of core to core faults
Uniform radial dielectric stresses in all section of the dielectric
No possibility of formation of voids within the dielectric
All of above
Reduced possibility of core to core faults
Screened cables (such as H-type cables) include a metallic sheath around each core insulation, which ensures that the electric field is purely radial and contained within each core. This construction eliminates the tangential stresses found in belted cables, leading to uniform dielectric stress and preventing the ionization of air voids.
Screened cables (such as H-type cables) include a metallic sheath around each core insulation, which ensures that the electric field is purely radial and contained within each core. This construction eliminates the tangential stresses found in belted cables, leading to uniform dielectric stress and preventing the ionization of air voids.
ErтАЛ=rln(R/r)VтАЛ тАФ Radial electric field stress in a cable
gmaxтАЛ=rln(R/r)VтАЛ тАФ Maximum dielectric stress at the conductor surface
In a belted cable, the stress is non-uniform due to the triangular filler and the common belt, leading to tangential forces that cause air void formation. By using individual metallic screens (usually perforated aluminum foil or copper tape), the electric field is forced to remain radial (perpendicular to the conductor), effectively reducing stress concentration and the probability of electrical breakdown.
Belted cables are limited to voltages below 11 kV due to tangential stress.
Screened cables allow for higher voltage ratings (up to 33 kV and beyond).
Metallic screens act as an equipotential surface, eliminating tangential components of electric stress.
Void formation is suppressed as the field lines are constrained within the core insulation.
Uniform radial stress distribution
Lower risk of partial discharge
Suitable for high voltage operation
Better heat dissipation
Higher manufacturing cost
Increased cable diameter and weight
High voltage underground power transmission
Submarine power cables
| Feature | Belted Cable | Screened Cable |
|---|---|---|
Stress Type | Radial and Tangential | Radial only |
Voltage Limit | Up to 11 kV | Up to 66 kV |
H-type cables and SL-type (Separate Lead) cables are common examples of screened construction.
Option A is correct because the metallic screen prevents electrical breakdown between phases.
Option B is correct because the screen creates an equipotential surface, ensuring the field lines remain radial.
D is correct тАФ Screened cables improve performance by ensuring purely radial dielectric stress and preventing air-void-related insulation failures.
Always remember that the transition from belted to screened cables is the primary reason the maximum voltage rating for underground AC cables increased from 11 kV to 33 kV.