Series capacitor
Increases the power transmission capability of EHV long line
Provides voltage control
Increases shunt admittance of line
None of above
Increases the power transmission capability of EHV long line
A series capacitor is connected in series with the transmission line to compensate for the inductive reactance of the line. By reducing the effective series reactance, it significantly increases the steady-state power transfer capability and enhances transient stability of EHV (Extra High Voltage) transmission systems.
A series capacitor is connected in series with the transmission line to compensate for the inductive reactance of the line. By reducing the effective series reactance, it significantly increases the steady-state power transfer capability and enhances transient stability of EHV (Extra High Voltage) transmission systems.
P=XLтАЛтИТXCтАЛV1тАЛV2тАЛтАЛsin╬┤ тАФ Power transfer with series compensation
QCтАЛ=I2XCтАЛ тАФ Reactive power generated by the series capacitor
The power transferred through a line is given by P=XLтАЛV1тАЛV2тАЛтАЛsin╬┤, where XLтАЛ is the inductive reactance. When a series capacitor with reactance XCтАЛ is added, the effective reactance becomes XeffтАЛ=XLтАЛтИТXCтАЛ. Since XeffтАЛ<XLтАЛ, the denominator decreases, causing the power transmission capability (PmaxтАЛ) to increase for a given load angle ╬┤.
Reduces the voltage drop across the line for a given load current.
Improves system steady-state and transient stability limits.
Provides self-regulation: as current increases, voltage support from the capacitor increases.
Requires protective equipment like spark gaps or MOV (Metal Oxide Varistors) to prevent overvoltages during faults.
Increased power transfer capability
Improved voltage profile
Enhanced transient stability
Flexible load sharing between parallel lines
Risk of sub-synchronous resonance (SSR)
High cost of protection equipment
Potential for ferro-resonance
Complexity in relay coordination
Long EHV and UHV transmission lines
Inter-regional power transfer grids
Heavy load center supply lines
Degree of compensation (k) is defined as XCтАЛ/XLтАЛ. Typically, k is chosen between 25% to 70%.
Option B is incorrect because voltage control is primarily the function of shunt compensation (like SVC or Synchronous Condensers).
Option C is incorrect because shunt admittance relates to shunt capacitors or reactors, not series capacitors.
A is correct тАФ A series capacitor reduces the net inductive reactance of the transmission line, thereby increasing its power transfer limit.
Always remember: Series capacitors improve stability (power limit), while shunt capacitors are used for voltage regulation (voltage profile).