The conductors of EHV line is selected on the basis of
Current carrying capacity
Corona
Line voltage
None of above
Corona
In Extra High Voltage (EHV) transmission lines, the conductor size is primarily determined by the phenomena of corona discharge rather than current-carrying capacity. For lines operating above 230 kV, increasing the conductor surface area is essential to reduce the surface voltage gradient and maintain it below the disruptive critical voltage of air.
In Extra High Voltage (EHV) transmission lines, the conductor size is primarily determined by the phenomena of corona discharge rather than current-carrying capacity. For lines operating above 230 kV, increasing the conductor surface area is essential to reduce the surface voltage gradient and maintain it below the disruptive critical voltage of air.
EmaxтАЛ=rln(D/r)VтАЛ тАФ Maximum electric field intensity at the surface of a conductor
VcтАЛ=moтАЛgoтАЛ╬┤rln(D/r) тАФ Disruptive critical voltage for corona inception
Corona occurs when the electric field strength at the conductor surface exceeds the dielectric strength of air (approx30kV/cm peak). To prevent this, the conductor diameter is increased (often using bundle conductors), which reduces the surface potential gradient E=rln(D/r)VтАЛ. By increasing r, the maximum electric field intensity E decreases, thus minimizing corona loss, radio interference, and audible noise.
Corona loss is proportional to (f+25)DrтАЛтАЛ(VтИТVcтАЛ)2
Bundle conductors are used in EHV lines to increase the effective radius, effectively reducing the voltage gradient.
Current carrying capacity (thermal limit) is the governing factor for low/medium voltage lines, while corona governs EHV/UHV lines.
Radio interference and audible noise are direct consequences of high corona activity.
Reduces energy loss due to ionization
Minimizes electromagnetic interference (EMI) with communication lines
Increases the power transfer capability of the transmission line
Larger conductors increase structural weight and tower cost
Increased surface area leads to higher wind/ice loading
400 kV Transmission Lines
765 kV and UHV DC Transmission systems
Standard conductor sizes for 400 kV are chosen to keep the maximum surface gradient below the critical breakdown value of air.
Option A is the governing factor for low-voltage distribution lines, but not EHV lines.
B is correct тАФ EHV conductors are chosen primarily to keep the surface voltage gradient below the corona inception limit, thereby preventing excessive power loss and noise.
Always remember: Thermal limit (Current) dominates for low voltages; Corona limit (Voltage) dominates for extra-high voltages (EHV).