The contact resistance of a circuit breaker is. of the order of
200 ohms ┬▒ 10
20milli ohms ┬▒ 10
20 ohms ┬▒ 10
20 micro ohms ┬▒ 10
20 micro ohms ┬▒ 10
The contact resistance of a high-voltage circuit breaker is extremely small, typically in the order of 20┬а╬╝╬й┬▒10┬а╬╝╬й (micro-ohms). Low contact resistance is crucial to prevent excessive I2R power loss and localized heating during normal continuous current carrying conditions.
IEC 62271-100 / IS 13118:1991 (Cl. 6.4 - Measurement of the resistance of circuits)
The contact resistance of a high-voltage circuit breaker is extremely small, typically in the order of 20┬а╬╝╬й┬▒10┬а╬╝╬й (micro-ohms). Low contact resistance is crucial to prevent excessive I2R power loss and localized heating during normal continuous current carrying conditions.
RcontactтАЛ=RcтАЛ+RfтАЛ тАФ total contact resistance (constriction + film resistance)
PlossтАЛ=I2RcontactтАЛ тАФ power loss at breaker contacts
RcтАЛтИЭFn╧БтАЛ тАФ constriction resistance in terms of resistivity ╧Б and contact force F
Circuit breaker contacts consist of fixed and moving contacts made of copper or silver-plated alloys. The contact resistance comprises constriction resistance (RcтАЛ) due to micro-scale surface roughness (asperities) and film resistance (RfтАЛ) due to surface oxidation or tarnish. High contact pressure and silver plating minimize both factors to keep the total resistance in the micro-ohm range.
Contact resistance is measured using a Micro-Ohmmeter (Digital Low Resistance Ohmmeter - DLRO) via the 4-wire Kelvin bridge method.
Standard test current specified by IEC standards is typically 100┬аA DC or higher.
Higher contact resistance leads to overheating, oxidation, thermal runaway, and potential contact welding.
Extremely low micro-ohm resistance minimizes steady-state power loss during high-current carrying.
Prevents excessive temperature rise, ensuring insulation life and operating safety.
Requires periodic maintenance and high contact spring pressure to be maintained.
Contact erosion during arcing increases contact resistance over time.
High-voltage and medium-voltage circuit breakers (SF6, Vacuum, Air Blast).
Isolators, disconnectors, and busbar contacts in electrical substations.
Typical contact resistance for HV circuit breakers ranges between 10┬а╬╝╬й to 50┬а╬╝╬й.
Option A (200┬а╬й), Option B (20┬аm╬й), and Option C (20┬а╬й) are excessively high values that would cause immediate destruction due to thermal runaway under thousands of amperes of rated current.
D is correct тАФ The contact resistance of a high-voltage circuit breaker is on the order of 20┬а╬╝╬й┬▒10┬а╬╝╬й to handle heavy currents without excessive heating.
In competitive exams, remember that power transformer winding resistance is in ohms/milli-ohms, whereas breaker contact resistance and busbar joint resistance are always in micro-ohms (10тИТ6┬а╬й).