Join 60,000+ competitive exam aspirants
The resistance between terminals of poles is too high in CB. which of the following is not a suitable reason?
Contact surface damaged
Contact pressure reduced
Moisture deposited
Oxide film on the contact surface
Moisture deposited
Contact resistance in circuit breaker poles is primarily governed by the effective contact surface area, contact pressure, and the presence of resistive surface films (such as oxides). Moisture deposited on the contacts may cause corrosion or insulation degradation over time, but it does not directly act as a high-resistance film layer like oxidation or mechanical surface degradation.
IEC 62271-100 / IS 13118 (High-Voltage Switchgear and Controlgear)
Contact resistance in circuit breaker poles is primarily governed by the effective contact surface area, contact pressure, and the presence of resistive surface films (such as oxides). Moisture deposited on the contacts may cause corrosion or insulation degradation over time, but it does not directly act as a high-resistance film layer like oxidation or mechanical surface degradation.
RcontactтАЛ=RcтАЛ+RfтАЛ тАФ Total contact resistance as sum of constriction and film resistance
RcтАЛ=2a╧БтАЛ тАФ Constriction resistance, where a is radius of contact area and ╧Б is resistivity
P=FspringтАЛ тАФ Contact pressure affects micro-contact area aтИЭFтАЛ
The electrical contact resistance consists of constriction resistance (RcтАЛ) and film/surface resistance (RfтАЛ). Contact surface damage reduces effective contact area, while reduced contact pressure leads to lower microscopic contact points (a-spots), both significantly increasing RcтАЛ. An oxide film acts as an insulating layer increasing RfтАЛ. Moisture, however, is a liquid dielectric layer and does not directly form a high-resistance surface oxide or constrict current flow paths in the short term.
Contact resistance consists of constriction resistance (RcтАЛ) and surface film resistance (RfтАЛ).
Damaged or rough surfaces reduce effective micro-contact points (a-spots), raising RcтАЛ.
Reduced spring/contact pressure lowers deformation at contact points, decreasing contact area and raising RcтАЛ.
Oxide films act as thin insulating layers, directly increasing film resistance (RfтАЛ).
Moisture deposition primary affects external/dielectric insulation breakdown rather than terminal contact resistance.
Option A: Contact surface damage reduces effective contact area a, increasing constriction resistance RcтАЛ. Thus, it is a valid reason.
Option B: Lower contact pressure reduces real contact area, directly increasing RcтАЛ. Thus, it is a valid reason.
Option D: Oxidation forms a non-conducting oxide layer on contacts, directly increasing film resistance RfтАЛ. Thus, it is a valid reason.
Option C: Moisture deposition leads to insulation degradation or flashover across poles, but does not increase contact resistance between closed terminals.
C is correct тАФ Moisture deposition primarily affects dielectric insulation strength rather than the contact surface resistance between terminals of circuit breaker poles.
In Switchgear & Protection exam questions, distinguish carefully between factors affecting 'Contact Resistance' (mechanical/surface film properties) versus 'Dielectric Strength / Breakdown' (moisture, air gap, temperature).