The wattmeter method is used to measure power in a three-phase load. The wattmeter readings are 200 W and тИТ35 W. Find the respective values of active power and reactive power.





In the two-wattmeter method for measuring three-phase power, the total active power (P) is the sum of the individual wattmeter readings (W1тАЛ+W2тАЛ), and the total reactive power (Q) is given by 3тАЛ(W1тАЛтИТW2тАЛ). Given W1тАЛ=200┬аW and W2тАЛ=тИТ35┬аW, the calculation follows directly from these formulas.
In the two-wattmeter method for measuring three-phase power, the total active power (P) is the sum of the individual wattmeter readings (W1тАЛ+W2тАЛ), and the total reactive power (Q) is given by 3тАЛ(W1тАЛтИТW2тАЛ). Given W1тАЛ=200┬аW and W2тАЛ=тИТ35┬аW, the calculation follows directly from these formulas.
P=W1тАЛ+W2тАЛ тАФ Total active power
Q=3тАЛ(W1тАЛтИТW2тАЛ) тАФ Total reactive power
The two-wattmeter method relies on Blondel's Theorem, which states that for an n-wire system, nтИТ1 wattmeters are required to measure total power. By connecting the current coils in two lines and the potential coils between those respective lines and the third line, the total power is derived from the algebraic sum of the readings. When one reading is negative, it indicates a power factor less than 0.5 (specifically, the phase angle between phase voltage and current exceeds 60┬░).
When W2тАЛ is negative, the load is highly inductive or capacitive, meaning the phase angle is greater than 60┬░.
Active power P=200+(тИТ35)=165┬аW.
Reactive power Q=3тАЛ(200тИТ(тИТ35))=3тАЛ(235)=2353тАЛ┬аVAR.
Requires only two wattmeters for balanced or unbalanced three-phase systems.
Provides information about both active power and reactive power (via difference in readings).
If the power factor is less than 0.5, one wattmeter will give a negative reading, requiring the reversal of its current coil leads for measurement.
Only applicable to three-wire systems.
Industrial motor power measurement.
General three-phase power monitoring.
The total power P is 200тИТ35=165┬аW.
The total reactive power Q is 3тАЛ├Ч(200тИТ(тИТ35))=2353тАЛ┬аVAR.
A is correct тАФ The active power is 165┬аW and the reactive power is 2353тАЛ┬аVAR.
Always remember that for Q=3тАЛ(W1тАЛтИТW2тАЛ), the sign convention depends on which reading is larger; a negative reading signifies that the phase angle between line voltage and phase current is greater than 60┬░.