What is maximum and minimum control voltage for closing and opening operation of Solenoid in the circuit breaker?
110%, 85%
120%, 80%
125%, 75%
110%, 90%
110%, 85%
In high-voltage circuit breakers, operating solenoids are standardized to function reliably within specific auxiliary voltage supply ranges. For tripping (opening) operations, high reliability is vital, so the operating voltage range is typically 70% to 110% of rated voltage. For closing solenoids, the operating range is 85% to 110% of rated voltage to prevent incomplete closing mechanism engagement under low voltage conditions.
IEC 62271-100 / IS 13118 Cl. 5.7
In high-voltage circuit breakers, operating solenoids are standardized to function reliably within specific auxiliary voltage supply ranges. For tripping (opening) operations, high reliability is vital, so the operating voltage range is typically 70% to 110% of rated voltage. For closing solenoids, the operating range is 85% to 110% of rated voltage to prevent incomplete closing mechanism engagement under low voltage conditions.
VmaxтАЛ=1.10├ЧVnominalтАЛ тАФ Maximum allowed operating control voltage (110%)
Vmin,closeтАЛ=0.85├ЧVnominalтАЛ тАФ Minimum allowed closing coil control voltage (85%)
Circuit breaker closing coils (solenoids) require a higher minimum threshold voltage (85% of nominal) to ensure sufficient force is generated to overcome strong opening springs and contact resistance. Tripping coils require a lower minimum operating limit (70% or 75%) so that breaker protection can operate even during severe DC battery voltage drops during a station power fault.
Closing operation requires 85% to 110% of rated auxiliary control voltage.
Tripping (opening) operation requires 70% to 110% of rated auxiliary control voltage.
Auxiliary supply voltages are typically 110 V DC or 220 V DC station batteries.
Prevents partial closure or damaging arcing across circuit breaker main contacts.
Guarantees protection trip functionality during severe auxiliary battery voltage dips.
Requires high-capacity station batteries to maintain voltage under load spikes.
Substation auxiliary DC system design.
Protection and control scheme specification for EHV and HV circuit breakers.
Per IEC standards, closing coils must close reliably at 85%-110% rated voltage, while trip coils operate down to 70% rated voltage.
Option A gives the standard statutory values in percentage terms relative to a nominal 100% supply (110% maximum and 85% minimum for closing).
A is correct тАФ The maximum control voltage limit for circuit breaker solenoids is 110% and the minimum for closing operation is 85% of rated voltage.
Remember: Trip coils always have a lower minimum voltage threshold (70%) compared to close coils (85%) because clearing a fault is safety-critical even during deep station battery discharge.