What should be the location of Lightning Arrester use for the protection of the substation?
At the highest high of the protecting equipment
near the apparatus to be protected
At the entry and the exit of substation
All of these
near the apparatus to be protected
A lightning arrester (surge arrester) must be strategically placed to divert high-voltage surges away from sensitive substation equipment to the ground. Placing them at entry/exit points intercepts incoming surges from transmission lines, while proximity to the apparatus minimizes the protective distance to ensure the voltage at the terminal remains below the equipment's Basic Insulation Level (BIL).
A lightning arrester (surge arrester) must be strategically placed to divert high-voltage surges away from sensitive substation equipment to the ground. Placing them at entry/exit points intercepts incoming surges from transmission lines, while proximity to the apparatus minimizes the protective distance to ensure the voltage at the terminal remains below the equipment's Basic Insulation Level (BIL).
VresтАЛ<VBILтАЛ тАФ The residual voltage of the arrester must be lower than the Basic Insulation Level of the equipment.
IsurgeтАЛ=ZsurgeтАЛVsurgeтАЛтИТVarrтАЛтАЛ тАФ Calculation of surge current diverted through the arrester.
The lightning arrester operates on the principle of non-linear resistance; it offers very high impedance at normal operating voltages and extremely low impedance during an overvoltage transient. By providing a low-impedance path to the ground at critical nodes, it shunts the surge current (IsurgeтАЛ) effectively, protecting the internal windings and insulation of transformers and switchgear.
Arresters are connected in parallel with the protected equipment.
Proximity is crucial; the lead length must be kept to a minimum to reduce lead inductance which causes inductive voltage drop (VLтАЛ=LdtdiтАЛ).
They must be located at the entry points of the substation to prevent surge penetration from the transmission lines.
Prevents catastrophic failure of power transformers.
Limits transient overvoltages to safe levels.
Improves system reliability and reduces downtime.
Requires periodic inspection for degradation.
Can fail if discharge capacity is exceeded by direct massive lightning strikes.
HV/EHV Transformer protection.
Substation busbar protection.
Circuit breaker and isolator protection.
The protection range depends on the steepness of the wave front; shorter distances are required for steeper fronts.
Option A is partially correct but incomplete; Option B is correct for local protection, and Option C is correct for line protection.
D is correct тАФ Lightning arresters must be installed at all critical points, including incoming lines and near protected apparatus, to ensure comprehensive coverage against surge transients.
Always remember that lead inductance significantly increases the voltage across an arrester during a transient; therefore, physical placement as close as possible to the protected equipment is a fundamental rule in switchgear design.