Join 60,000+ competitive exam aspirants
Which of the following results in a symmetrical fault?
Single phase to earth
Phase to phase
All the three phase to earth
Two phase to earth
All the three phase to earth
A symmetrical fault, also known as a balanced fault, is a fault in a power system where all three phases of the system are affected equally, maintaining the symmetry of the phases ┬╖ This results in balanced fault currents that are identical in magnitude and displaced by 120┬░ electrical degrees.
A symmetrical fault, also known as a balanced fault, is a fault in a power system where all three phases of the system are affected equally, maintaining the symmetry of the phases ┬╖ This results in balanced fault currents that are identical in magnitude and displaced by 120┬░ electrical degrees.
IfтАЛ=Z1тАЛVphтАЛтАЛ тАФ Current for a balanced three-phase fault where Z1тАЛ is the positive sequence impedance.
ZeqтАЛ=Z1тАЛ тАФ For symmetrical faults, only the positive sequence network is considered.
In a three-phase system, a fault involving all three phases (either with or without a connection to the ground) disrupts the system symmetry minimally because the impedance paths for each phase remain identical ┬╖ Consequently, the fault currents calculated using the per-phase equivalent circuit are balanced, satisfying the condition for a symmetrical fault analysis.
Symmetrical faults are rare (only about 2-5% of total faults) but are the most severe.
The fault current is calculated using only the positive sequence network.
The power system remains balanced during and after the occurrence of the fault.
Three-phase to earth (LLL-G) and Three-phase (LLL) are both symmetrical faults.
Simplifies power system analysis using single-phase equivalent circuits.
Provides the worst-case scenario for determining circuit breaker rupturing capacity.
Extremely high thermal and mechanical stresses on power equipment.
Significant voltage dips across the entire interconnected grid.
Determination of maximum fault current.
Selection and rating of switchgear and circuit breakers.
| Feature | LLL or LLL-G | SLG, LL, LL-G |
|---|---|---|
Fault Classification | Symmetrical | Asymmetrical |
The vast majority of faults (approx. 80%) are Single Line-to-Ground (SLG) faults, which are asymmetrical.
Options A, B, and D describe asymmetrical faults because they cause unequal impedance paths and phase imbalance in the system.
C is correct тАФ All three phases to earth (LLL-G) is a symmetrical fault because it affects all three phases equally, maintaining phase balance.
Always remember that for symmetrical faults, the neutral current is zero (InтАЛ=0) because the three-phase currents sum to zero at the neutral point.