Which one of the following statements is NOT true for synchronous motor used for power factor improvement in comparison with static condenser
Its maintenance is more
It operates at zero leading power factor only
It requires D. C. supply
It requires more space
It requires D. C. supply
The statement 'It operates at zero leading power factor only' is false because a synchronous condenser can be operated at a variable power factor (lagging, unity, or leading) by adjusting the field excitation. Option C is technically true, as a synchronous motor requires a separate DC supply for its rotor field winding.
The statement 'It operates at zero leading power factor only' is false because a synchronous condenser can be operated at a variable power factor (lagging, unity, or leading) by adjusting the field excitation. Option C is technically true, as a synchronous motor requires a separate DC supply for its rotor field winding.
Q=VIrтАЛsin(╧Х) тАФ Reactive power control based on excitation
EbтАЛ=14.44f╬жNKwтАЛтАЛ тАФ Induced EMF depends on flux ╬ж adjusted via DC current
A synchronous condenser acts as a variable reactive power source. When over-excited, it behaves like a capacitor (supplying reactive power), and when under-excited, it behaves like an inductor (absorbing reactive power). The degree of leading or lagging VARs is controlled solely by varying the DC excitation current in the rotor winding.
Synchronous condensers are large synchronous motors running at no load.
They provide smooth, continuous control of reactive power.
Over-excitation provides leading VARs for power factor correction.
Unlike static capacitors, they can compensate for both lagging and leading reactive power.
Smooth and stepless reactive power control
Voltage regulation capabilities
Higher thermal stability
High maintenance due to rotating parts
Requires DC source and starter
Generates acoustic noise
Large scale industrial power factor correction
Voltage stability in high voltage transmission lines
| Feature | Synchronous Motor | Static Condenser |
|---|---|---|
Control | Variable/Stepless | Fixed/Stepped |
The phrase 'zero leading power factor' implies an ideal capacitor, whereas a synchronous motor has resistive losses, meaning it can never reach a purely theoretical zero power factor angle.
Static condensers (banks of capacitors) are maintenance-free but provide fixed reactive power.
B is the correct choice to identify as 'NOT true' because synchronous motors provide variable, not just zero-leading, power factor.
Always remember that static capacitors are passive elements, while synchronous motors are active rotating machines requiring a DC excitation system.