Join 60,000+ competitive exam aspirants
With bundled conductors
Corona inception voltage increases
Corona inception voltage decreases
Corona inception voltage remains unaffected
None of above
Corona inception voltage increases
Bundled conductors increase the effective radius of the transmission line, which significantly reduces the surface voltage gradient. Since the corona inception voltage is directly proportional to the effective radius of the conductor, bundling leads to an increase in the corona inception voltage.
Bundled conductors increase the effective radius of the transmission line, which significantly reduces the surface voltage gradient. Since the corona inception voltage is directly proportional to the effective radius of the conductor, bundling leads to an increase in the corona inception voltage.
VcтАЛ=g0тАЛтЛЕ╬┤тЛЕmтЛЕrтЛЕln(rDтАЛ) тАФ Corona inception voltage formula
E=rln(rDтАЛ)VтАЛ тАФ Electric field intensity at conductor surface
Corona inception depends on the electric field intensity at the conductor surface, given by E=rln(D/r)VтАЛ. By using bundled conductors, the geometric mean radius (GMR) increases. This increase in effective radius (reffтАЛ) reduces the surface stress for a given applied voltage, delaying the air ionization process and thereby increasing the inception voltage.
Bundling increases the Geometric Mean Radius (GMR) of the conductor arrangement.
Higher effective radius reduces the maximum electric field stress on the surface.
Corona loss is inversely proportional to the square of the inception voltage.
Bundled conductors improve transmission efficiency by reducing corona loss and radio interference.
Reduced corona loss
Lower line reactance (reduced inductance)
Higher surge impedance loading (SIL)
Reduced radio and television interference
Increased wind load on towers
Complex hardware requirements (spacers)
Increased cost of installation
Extra High Voltage (EHV) lines (400 kV and above)
Ultra High Voltage (UHV) transmission lines
The corona inception voltage (VcтАЛ) is the critical voltage at which the dielectric strength of air breaks down.
Option B is incorrect because bundling reduces surface stress, which pushes the threshold for ionization to a higher voltage level.
A is correct тАФ Bundled conductors increase the effective radius of the line, which decreases the surface voltage gradient and consequently increases the corona inception voltage.
Always remember that any design change increasing the effective surface area of a conductor (like bundling or increasing radius) helps in mitigating corona effects by lowering surface potential gradient.