Join 60,000+ competitive exam aspirants
Zero sequence fault currents are absent when the fault is
Single line to ground
Line to line
Double line to ground
Any of above
Line to line
Zero sequence currents (I0) depend on the presence of a path to the ground for the fault current to flow. In a line-to-line (L-L) fault, the fault involves only two phases with no connection to the neutral or ground, hence the sum of the phase currents remains zero, resulting in zero sequence current.
Zero sequence currents (I0) depend on the presence of a path to the ground for the fault current to flow. In a line-to-line (L-L) fault, the fault involves only two phases with no connection to the neutral or ground, hence the sum of the phase currents remains zero, resulting in zero sequence current.
I0=31(Ia+Ib+Ic) — Definition of zero sequence current
Ia+Ib+Ic=3I0 — Relationship between phase currents and zero sequence current
In symmetrical component analysis, the phase currents are decomposed into positive, negative, and zero sequence components. The zero sequence current is defined as I0=31(Ia+Ib+Ic). In a line-to-line fault, since there is no ground path, Ia+Ib+Ic=0, leading to I0=0.
Zero sequence currents only exist if the fault involves ground.
L-G and LL-G faults involve ground, so they contain zero sequence components.
L-L faults and three-phase balanced faults do not involve ground, resulting in I0=0.
Positive and negative sequence components exist in all unsymmetrical faults.
Simplifies fault analysis by identifying zero sequence network conditions.
Helps in determining relay settings for ground fault protection.
Does not provide information about the magnitude of positive or negative sequence currents.
Power system relay coordination
Grounding transformer design
Fault current studies
In a perfectly balanced 3-phase system, Ia+Ib+Ic=0, meaning I0=0.
Option A (L-G) and Option C (LL-G) involve the ground, therefore they produce I0=0.
B is correct — A line-to-line fault does not involve the ground, therefore the sum of the phase currents is zero, which results in zero sequence current being absent.
Remember: If a fault does not touch the ground, the zero sequence network is effectively open-circuited.