3 MW power is transmitted over a distance of 30 km, the desirable transmission voltage is
11 kV
33 kV
66 kV
3 kV
66 kV
For power transmission, the choice of voltage is governed by the empirical 'Thomsons's Law' and economic considerations related to the distance and power magnitude. For a power of 3 MW and a distance of 30 km, 66 kV is the standard and most economical voltage level to minimize conductor material cost and I2R losses.
For power transmission, the choice of voltage is governed by the empirical 'Thomsons's Law' and economic considerations related to the distance and power magnitude. For a power of 3 MW and a distance of 30 km, 66 kV is the standard and most economical voltage level to minimize conductor material cost and I2R losses.
P=3тАЛVLтАЛILтАЛcos╧Х тАФ Relation between power, voltage, and current
VlineтАЛтЙИ5.51.6lтАЛ+150PтАЛтАЛ тАФ Empirical formula used in Indian practice for transmission voltage in kV where l is distance in km and P is power in kW
The transmission voltage is primarily determined by the power rating and transmission distance. As voltage increases, current for a given power level decreases, leading to lower copper losses (I2R) and reduced conductor cross-sectional area requirements. However, higher voltages require increased insulation levels and costlier switchgear, necessitating an optimal balance.
Higher transmission voltage reduces current for the same power, lowering transmission losses.
The cost of the conductor material decreases as the transmission voltage increases.
Optimal voltage selection balances the cost of conductors versus the cost of transformers and insulation.
In India, 66 kV is a common sub-transmission voltage level for medium distances and power capacities.
Reduction in copper losses (I2R)
Improved voltage regulation
Increased transmission efficiency
Smaller conductor cross-section required
Higher insulation cost for lines and equipment
Increased tower size and clearance requirements
Higher cost of transformers and switchgear
Medium voltage distribution systems
Sub-transmission grids
Interconnecting small-scale power plants to the grid
According to the rule of thumb used in Indian Engineering services: Voltage(kV)тЙИ5.50.62├Чdistance(km)+150power(kVA)тАЛтАЛ.
Options like 3 kV and 11 kV are typically for distribution or short-distance industrial applications, while 33 kV is often used for shorter distances than 30 km.
C is correct тАФ 66 kV is the optimal transmission voltage for transferring 3 MW over 30 km based on standard power system design practices.
Always remember that for transmission voltage selection, if the formula is not provided, follow the trend: Power and Distance increase => Voltage must increase to maintain efficiency.