Join 60,000+ competitive exam aspirants
A 66 kV system has string insulator having five discs and the earth to disc capacitance ratio of 0.10. The string efficiency will be
89%
75%
67%
55%
67%
C is correct because the calculated string efficiency for n=5 and k=0.1 is approximately 67-69%, which is closest to the provided option 67%.
Number of discs n = 5, Ratio of shunt capacitance to mutual capacitance k = 0.10
η=n×VnV×100
Calculate voltages across each disc
Let V1 be the voltage across the disc nearest to the conductor. Using the ratio k=0.1, the voltages are: V2=V1(1+k)=1.1V1, V3=V1(1+3k+k2)=1.31V1, V4=V1(1+6k+5k2+k3)=1.611V1, V5=V1(1+10k+15k2+7k3+k4)=2.0511V1.
V2=1.1V1,V3=1.31V1,V4=1.611V1,V5=2.0511V1
Calculate total voltage of the string
The total voltage V across the string is the sum of voltages across each disc: V=V1+V2+V3+V4+V5. Summing these values gives V=(1+1.1+1.31+1.611+2.0511)V1=7.0721V1.
V=7.0721V1
Calculate string efficiency
String efficiency η is defined as the ratio of total voltage across the string to (n times the voltage across the disc nearest to the conductor).
η=5×2.0511V17.0721V1×100≈68.96%
C is correct because the calculated string efficiency for n=5 and k=0.1 is approximately 67-69%, which is closest to the provided option 67%.
String efficiency increases as the number of discs increases or if we use grading rings to equalize the voltage distribution across discs.