A lightning arrestor is usually located nearer to -
busbar
transformer
circuit breaker
isolator
transformer
A lightning arrestor is primarily designed to protect expensive, highly inductive equipment like transformers from high-voltage surges caused by lightning strikes or switching operations. To minimize the impedance of the discharge path and avoid the effects of traveling wave reflections that increase voltage at the equipment terminals, it is placed as physically close as possible to the transformer.
A lightning arrestor is primarily designed to protect expensive, highly inductive equipment like transformers from high-voltage surges caused by lightning strikes or switching operations. To minimize the impedance of the discharge path and avoid the effects of traveling wave reflections that increase voltage at the equipment terminals, it is placed as physically close as possible to the transformer.
VmaxтАЛ=2├ЧVsurgeтАЛ тАФ Theoretical doubling of voltage due to reflections at open-circuited terminals
ZsurgeтАЛ=CLтАЛтАЛ тАФ Surge impedance of the transmission line
When a surge voltage exceeds the breakdown voltage of the lightning arrestor, it provides a low-impedance path to the ground. By placing the arrestor near the transformer, the reflection coefficient at the junction limits the peak voltage spike reaching the transformer windings. The arrestor absorbs the energy of the surge and keeps the transient overvoltage below the Basic Insulation Level (BIL) of the transformer.
Lightning arrestors act as a surge diverter to ground.
Proximity is crucial to prevent surge voltage reflection doubling at the equipment terminals.
The discharge path impedance must be kept as low as possible.
The protection level is always coordinated with the Basic Insulation Level (BIL) of the transformer.
Protects costly transformer insulation from dielectric failure
Prevents catastrophic equipment damage during thunderstorms
Adds cost and maintenance complexity
Requires periodic testing of the non-linear resistors
Power transmission substations
Distribution transformer secondary and primary ends
The distance between the arrestor and the transformer should ideally be kept below 2-3 meters to avoid the traveling wave effect.
If the arrestor is placed too far, the inductive drop in the leads and the reflected wave can cause the voltage at the transformer terminal to exceed the arrestor's discharge voltage.
B is correct тАФ The lightning arrestor is installed nearest to the transformer to minimize the reflection of surge waves and keep the voltage across the transformer insulation below its withstand limit.
Always remember the rule 'The shorter the lead, the better the protection.' Excess lead length introduces extra inductance (LdtdiтАЛ), which can cause the voltage at the protected terminal to rise significantly during a fast-front lightning strike.