A null point of uniformly loaded distributor fed at equal voltage at both ends lies at
Midpoint
Either end
Two third distance from one end
One fourth distance from one end
Midpoint
In a uniformly loaded distributor fed at equal voltages from both ends, the voltage drop from each end increases as one moves towards the center. Because the potentials at the supply points are identical, the minimum voltage (null point of potential difference relative to the source) occurs exactly at the midpoint of the distributor.
In a uniformly loaded distributor fed at equal voltages from both ends, the voltage drop from each end increases as one moves towards the center. Because the potentials at the supply points are identical, the minimum voltage (null point of potential difference relative to the source) occurs exactly at the midpoint of the distributor.
VxтАЛ=VтИТ2iтЛЕRтАЛ(LxтИТx2) тАФ Voltage at distance x from one end
VminтАЛ=VтИТ8iтЛЕRтЛЕL2тАЛ тАФ Minimum voltage at midpoint
Consider a distributor of length L with a uniform load i (amperes per meter). When fed at both ends with voltage V, the voltage drop at a distance x from one end is determined by the integration of the current flow. Due to symmetry and equal supply potentials, the current flows from both ends towards the center, where the net current becomes zero, establishing the minimum potential point at x=L/2.
Voltage profile is parabolic for a uniformly distributed load.
The point of minimum potential is where the current flowing in the distributor is zero.
Symmetry ensures the point of minimum potential coincides with the point of zero current.
Equal end voltages lead to a symmetric potential dip.
Reduces total voltage drop compared to single-end feeding.
Increases the current carrying capacity of the system.
Provides better voltage regulation across the distributor.
Requires two separate substation feeds.
Increases system complexity and initial infrastructure costs.
Low voltage distribution networks in urban areas.
Industrial plant power distribution circuits.
If the end voltages were unequal, the null point would shift towards the end with the lower voltage.
Option B (Either end) is incorrect as voltage drop is maximum at the center for a single-fed line and minimum for a double-fed line.
A is correct тАФ For a distributor fed at equal voltages at both ends, the symmetry of the circuit ensures that the point of minimum voltage (null point) resides at the midpoint.
Always check for symmetry in power distribution questions; if the boundary conditions (source voltages) are equal, the point of extrema (min/max) often occurs at the spatial midpoint.