A uniformly loaded DC distributor is fed at both ends with equal voltages. In┬а comparison to similar distributor fed at one end only, The maximum voltage drop will be
One fourth
One half
One third
One sixth
One fourth
For a uniformly loaded DC distributor of length L fed at one end, the maximum voltage drop occurs at the far end and is given by 2iL2тАЛ, where i is load per unit length. When fed at both ends with equal voltages, the distributor effectively acts as two separate distributors of length L/2 each, reducing the maximum voltage drop to one-fourth of the single-end fed value.
For a uniformly loaded DC distributor of length L fed at one end, the maximum voltage drop occurs at the far end and is given by 2iL2тАЛ, where i is load per unit length. When fed at both ends with equal voltages, the distributor effectively acts as two separate distributors of length L/2 each, reducing the maximum voltage drop to one-fourth of the single-end fed value.
╬ФVsingleтАЛ=2iL2тАЛ тАФ Maximum voltage drop for single-end fed distributor
╬ФVbothтАЛ=2i(L/2)2тАЛ=41тАЛ╬ФVsingleтАЛ тАФ Maximum voltage drop for both-ends fed distributor
In a distributor fed at both ends, the point of minimum potential occurs at the midpoint. By splitting the length into two segments of L/2 each, the resistance and current flowing in each segment are halved, resulting in a voltage drop formula ╬ФV=2i(L/2)2тАЛ=41тАЛ├Ч2iL2тАЛ.
Maximum voltage drop occurs at the far end for single-end fed distributors.
Maximum voltage drop occurs at the midpoint for both-ends fed distributors.
The total resistance of the distributor is reduced by a factor of 4 effectively.
Voltage stability is significantly improved by feeding at both ends.
Lower voltage drop across the distributor
Improved voltage regulation
Increased load carrying capacity
Requires two feeding substations
Increased complexity in protection coordination
Large industrial areas
Urban power distribution networks
| Feature | Fed at one end | Fed at both ends |
|---|---|---|
Max Voltage Drop | iL2/2 | iL2/8 |
The load i is defined as the current per unit length (e.g., A/m).
Option B, C, and D are incorrect as they do not satisfy the quadratic relationship of the voltage drop formula with respect to length.
A is correct тАФ The maximum voltage drop in a uniformly loaded distributor fed at both ends is one-fourth of the drop when fed at only one end.
Remember that voltage drop in a uniformly loaded distributor is proportional to the square of the distance from the source; halving the distance reduces the drop to one-fourth.