Join 60,000+ competitive exam aspirants
A suspension type insulator has three units with self-capacitance C and ground capacitance of 0.2C having a string efficiency of
78%
80%
82%
84%
78%
A is correct because the calculated string efficiency based on the voltage distribution across three units is approximately 78%.
Number of insulators n = 3, self-capacitance C, ground capacitance K = 0.2C
η=n×VnV×100
Calculate the constant K
The ratio of shunt capacitance to self-capacitance is given as K=C0.2C=0.2.
K=0.2
Express voltages of units
Let V1 be the voltage across the unit near the conductor. The voltages are related as V2=V1(1+K) and V3=V1(1+3K+K2).
V2=V1(1.2),V3=V1(1+0.6+0.04)=1.64V1
Calculate total voltage
Total voltage V=V1+V2+V3=V1(1+1.2+1.64)=3.84V1.
V=3.84V1
Calculate string efficiency
String efficiency is η=3V3V=3×1.64V13.84V1=4.923.84≈0.7804.
η≈78%
A is correct because the calculated string efficiency based on the voltage distribution across three units is approximately 78%.
String efficiency can be improved by using a grading ring or increasing the number of strings, which is a common topic in high voltage transmission line design.