A system has connected load of 120 kW, peak load of 100 kW, base load of 25 kW, and average load of 48 kW. The load factor of the consumer is
40%
48%
25%
83.30%
48%
B is correct because the load factor is the ratio of average load to peak load, which calculates to 48%.
Connected load = 120 kW, Peak load = 100 kW, Base load = 25 kW, Average load = 48 kW
LF=Peak LoadAverage Load×100%
Identify required parameters
To calculate the Load Factor (LF), we only need the average load and the peak load. The connected load and base load are provided as extraneous information.
Average Load=48 kW,Peak Load=100 kW
Apply Load Factor formula
The load factor is defined as the ratio of average load to the maximum (peak) load over a specific period.
LF=10048×100%
Calculate final result
Simplifying the fraction gives the percentage value of the load factor.
LF=0.48×100=48%
B is correct because the load factor is the ratio of average load to peak load, which calculates to 48%.
In power systems, the load factor is always ≤1 (or ≤100%); values closer to 1 indicate a stable, efficient utilization of generation capacity.