Join 60,000+ competitive exam aspirants
A transformer has full load iron loss of 900 W and copper loss of 1600 W. At what percentage of the load the transformer will have maximum efficiency?
90 %
100 %
75 %
80 %
75 %
Maximum efficiency in a transformer occurs when the constant iron losses (core losses) are exactly equal to the variable copper losses. At this point, the efficiency curve reaches its peak relative to the load current.
Maximum efficiency in a transformer occurs when the constant iron losses (core losses) are exactly equal to the variable copper losses. At this point, the efficiency curve reaches its peak relative to the load current.
x=PcтАЛPiтАЛтАЛтАЛ тАФ The fraction of full load for maximum efficiency
PiтАЛ=I2R тАФ Principle where Iron Loss equals Copper Loss
Total loss PLтАЛ=PiтАЛ+x2PcтАЛ, where PiтАЛ is iron loss, PcтАЛ is full-load copper loss, and x is the fraction of full load. Efficiency ╬╖=xcdotScdotcos╧Х+PiтАЛ+x2PcтАЛxcdotScdotcos╧ХтАЛ. Differentiating with respect to x and setting to zero yields PiтАЛ=x2PcтАЛ. Thus, x=PcтАЛPiтАЛтАЛтАЛ.
Maximum efficiency occurs when constant losses equal variable losses.
Iron loss (PiтАЛ) is independent of load current.
Copper loss (PcтАЛ) is proportional to the square of the load current (I2).
The fraction x represents the load ratio (0 to 1).
Helps in optimal transformer design for specific load profiles.
Essential for energy conservation in power distribution.
Maximum efficiency is only achieved at a specific load point.
Varying loads throughout the day cause the transformer to operate below peak efficiency.
Distribution transformer sizing.
Industrial motor drive optimization.
Given PiтАЛ=900W and PcтАЛ=1600W.
Calculation: x=1600900тАЛтАЛ=0.5625тАЛ=0.75 or 75%.
Option B (100%) would only be correct if iron loss equaled copper loss at full load.
C is correct тАФ The load fraction is determined by the square root of the ratio of iron loss to full-load copper loss, yielding 75%.
Always remember the phrase 'Variable losses equal constant losses' to quickly find the loading point for maximum efficiency in any electrical machine.