A 500 kVA 2 winding transformer has an iron loss of 3 kW and a full load copper loss of 3.5 kW. Calculate the kVA loading for maximum efficiency.
345.6 kVA
320.0 kVA
462.9 kVA
240.0 kVA
462.9 kVA
Quick Summary: Practice and solve "A 500 kVA 2 winding transformer has an iron loss of 3 kW and a full load copper loss of 3.5 kW. Calc..." for Electrical - Machine. The correct answer is Option C: 462.9 kVA. Detailed step-by-step solution, conceptual clarity, and formulas on Examoogle.
Answer:
Option **(c) **