A transformer rated for 500 KVA, 1 KV/0.4 KV has an impedance of 10% and is connected to an infinite bus ┬╖ The fault level of the transformer is
500 KVA
5000 KVA
3тАЛ├Ч500┬аKVA
None of the above
5000 KVA
Given: Transformer rating S = 500 KVA, Per-unit Impedance ZpuтАЛ = 10% = 0.1, Infinite bus supply
Transformer rating S = 500 KVA, Per-unit Impedance ZpuтАЛ = 10% = 0.1, Infinite bus supply
Fault┬аLevel=ZpuтАЛRated┬аSтАЛ
Identify the Given Parameters
The transformer capacity is SratedтАЛ=500┬аKVA and the percentage impedance is given as Z%=10%.
ZpuтАЛ=10010тАЛ=0.1
Apply Fault Level Formula
When a transformer is connected to an infinite bus, the short circuit MVA (or KVA) is determined by its own impedance as the supply impedance is negligible.
Fault┬аLevel=ZpuтАЛSratedтАЛтАЛ
Calculate the Result
Substitute the values SratedтАЛ=500┬аKVA and ZpuтАЛ=0.1 into the formula to find the fault level.
Fault┬аLevel=0.1500тАЛ=5000┬аKVA
B is correct because the fault level is calculated by dividing the rated KVA by the per-unit impedance, resulting in 5000 KVA.
The concept of Short Circuit MVA (or KVA) is vital for selecting circuit breakers; a higher impedance limits the fault current, effectively reducing the fault level.